CVE-2025-48022

6.5 MEDIUM

📋 TL;DR

A vulnerability in Yokogawa's Vnet/IP Interface Package allows attackers to crash the Vnet/IP software stack by sending maliciously crafted packets. This affects industrial control systems using CENTUM VP R6 and R7 with the vulnerable interface package. The vulnerability can cause process termination leading to potential disruption of industrial operations.

💻 Affected Systems

Products:
  • Vnet/IP Interface Package for CENTUM VP R6 VP6C3300
  • Vnet/IP Interface Package for CENTUM VP R7 VP7C3300
Versions: R1.07.00 or earlier
Operating Systems: Not specified in advisory
Default Config Vulnerable: ⚠️ Yes
Notes: Affects specific CENTUM VP configurations with Vnet/IP Interface Package installed

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Denial of service causing industrial process disruption, potentially leading to production downtime or safety system impacts in critical infrastructure environments.

🟠

Likely Case

Service disruption requiring manual restart of affected Vnet/IP processes, causing temporary operational interruptions.

🟢

If Mitigated

Minimal impact with proper network segmentation and monitoring allowing quick detection and recovery.

🌐 Internet-Facing: LOW (Industrial control systems should never be directly internet-facing)
🏢 Internal Only: MEDIUM (Requires network access to industrial control network segment)

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires network access to send crafted packets to vulnerable interface

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: R1.08.00 or later

Vendor Advisory: https://web-material3.yokogawa.com/1/39281/files/YSAR-26-0002-E.pdf

Restart Required: Yes

Instructions:

1. Download updated Vnet/IP Interface Package from Yokogawa support portal. 2. Follow vendor installation procedures for CENTUM VP systems. 3. Restart affected services/systems as required.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate CENTUM VP systems in dedicated industrial control network segments with strict firewall rules

Traffic Filtering

all

Implement network filtering to restrict access to Vnet/IP ports from unauthorized sources

🧯 If You Can't Patch

  • Implement strict network access controls to limit which systems can communicate with CENTUM VP Vnet/IP interfaces
  • Deploy network monitoring and intrusion detection specifically for industrial control system traffic patterns

🔍 How to Verify

Check if Vulnerable:

Check Vnet/IP Interface Package version in CENTUM VP system configuration or contact Yokogawa support

Check Version:

Check through CENTUM VP system configuration interface or Yokogawa diagnostic tools

Verify Fix Applied:

Verify Vnet/IP Interface Package version is R1.08.00 or later in system configuration

📡 Detection & Monitoring

Log Indicators:

  • Unexpected Vnet/IP process terminations
  • Service restart events in CENTUM VP logs
  • Network connection attempts to Vnet/IP ports

Network Indicators:

  • Unusual traffic patterns to Vnet/IP ports (typically UDP 50020)
  • Malformed packet patterns targeting industrial protocols

SIEM Query:

source="centum-vp-logs" AND (event_type="process_termination" OR event_type="service_restart") AND process_name="vnet_ip"

🔗 References