CVE-2025-11788

9.8 CRITICAL

📋 TL;DR

A heap-based buffer overflow vulnerability in Circutor SGE-PLC1000/SGE-PLC50 allows remote code execution by sending an excessively large 'meter' parameter. This affects industrial control systems using these specific PLC models, potentially enabling attackers to take full control of the device.

💻 Affected Systems

Products:
  • Circutor SGE-PLC1000
  • Circutor SGE-PLC50
Versions: v9.0.2
Operating Systems: Embedded PLC firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Affects the specific firmware version; other versions may also be vulnerable but unconfirmed.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete system compromise leading to remote code execution, device takeover, and potential lateral movement within industrial networks.

🟠

Likely Case

Remote code execution allowing attackers to manipulate PLC operations, disrupt industrial processes, or establish persistence.

🟢

If Mitigated

Limited impact if devices are isolated in air-gapped networks with strict input validation at perimeter controls.

🌐 Internet-Facing: HIGH - CVSS 9.8 indicates critical severity for remotely exploitable vulnerabilities.
🏢 Internal Only: HIGH - Even internally, successful exploitation could compromise critical industrial control systems.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Direct buffer overflow via user-controlled input suggests straightforward exploitation once details are public.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Unknown

Vendor Advisory: https://www.incibe.es/en/incibe-cert/notices/aviso-sci/multiple-vulnerabilities-circutor-products-0

Restart Required: Yes

Instructions:

1. Monitor Circutor for firmware updates. 2. Apply vendor-provided patches when available. 3. Restart affected PLC devices after patching.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate affected PLCs in dedicated industrial network segments with strict firewall rules.

Input Validation Proxy

all

Deploy a proxy that validates and sanitizes all 'meter' parameter inputs before reaching the PLC.

🧯 If You Can't Patch

  • Implement strict network access controls to limit communication to trusted sources only.
  • Monitor network traffic for anomalous parameter sizes in requests to the vulnerable function.

🔍 How to Verify

Check if Vulnerable:

Check device firmware version via web interface or serial console; if version is v9.0.2, device is vulnerable.

Check Version:

Check via web interface at http://<PLC_IP>/status or via serial console using vendor-specific commands.

Verify Fix Applied:

Verify firmware version has been updated to a patched release from Circutor.

📡 Detection & Monitoring

Log Indicators:

  • Unusually large parameter values in HTTP requests
  • Multiple failed buffer overflow attempts
  • Unexpected process crashes or restarts

Network Indicators:

  • HTTP requests with meter parameter exceeding normal size (e.g., >1000 characters)
  • Traffic patterns indicating exploitation attempts

SIEM Query:

source="plc_logs" AND (meter_parameter_length>1000 OR buffer_overflow_detected)

🔗 References

📤 Share & Export