CVE-2022-34759

7.5 HIGH

📋 TL;DR

This CVE describes an out-of-bounds write vulnerability in Schneider Electric's X80 advanced RTU and OPC UA Modicon communication modules. Improper parsing of HTTP headers could allow attackers to cause denial of service of the webserver. Organizations using affected Schneider Electric industrial control system components are at risk.

💻 Affected Systems

Products:
  • X80 advanced RTU Communication Module (BMENOR2200H)
  • OPC UA Modicon Communication Module (BMENUA0100)
Versions: BMENOR2200H V1.0; BMENUA0100 V1.10 and prior
Operating Systems: Embedded firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Affects the webserver component specifically; other functions may continue operating.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete denial of service of the webserver component, potentially disrupting industrial control system communications and operations.

🟠

Likely Case

Webserver crash leading to temporary loss of web interface functionality until manual restart.

🟢

If Mitigated

Minimal impact if systems are behind proper network segmentation and have restricted HTTP access.

🌐 Internet-Facing: HIGH - Internet-facing devices could be easily targeted for DoS attacks.
🏢 Internal Only: MEDIUM - Internal attackers or malware could exploit this to disrupt operations.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

The vulnerability requires sending specially crafted HTTP headers to the webserver interface.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Check Schneider Electric security advisory for specific patched versions

Vendor Advisory: https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2022-193-01_OPC_UA_X80_Advanced_RTU_Modicon_Communication_Modules+_Security_Notification.pdf

Restart Required: Yes

Instructions:

1. Download firmware update from Schneider Electric portal. 2. Follow vendor's firmware update procedure for affected modules. 3. Restart devices after update.

🔧 Temporary Workarounds

Network segmentation

all

Isolate affected devices in dedicated network segments with restricted HTTP access

Access control lists

all

Implement firewall rules to restrict HTTP access to trusted sources only

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate affected devices
  • Disable web interface if not required for operations

🔍 How to Verify

Check if Vulnerable:

Check device firmware version against affected versions listed in vendor advisory

Check Version:

Check via device web interface or Schneider Electric configuration tools

Verify Fix Applied:

Verify firmware version has been updated to patched version from Schneider Electric

📡 Detection & Monitoring

Log Indicators:

  • Webserver crash logs
  • Unusual HTTP header patterns in access logs

Network Indicators:

  • Malformed HTTP requests to device web interfaces
  • Sudden loss of web service

SIEM Query:

source="industrial_device" AND (http_request contains "malformed_header" OR status="crash")

🔗 References

📤 Share & Export