CVE-2022-30313

7.5 HIGH

📋 TL;DR

Honeywell Experion PKS Safety Manager lacks authentication on proprietary protocols, allowing unauthenticated attackers to manipulate controller state, configuration, logic, files, and I/O. Affected systems include Honeywell Experion PKS Safety Manager installations using Experion TCP (51000/TCP) and Safety Builder (51010/TCP) protocols through May 6, 2022.

💻 Affected Systems

Products:
  • Honeywell Experion PKS Safety Manager
Versions: All versions through 2022-05-06
Operating Systems: Proprietary industrial control system
Default Config Vulnerable: ⚠️ Yes
Notes: Physical keyswitch position provides some mitigation for certain functions, but many critical operations remain vulnerable.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete compromise of industrial safety systems leading to process disruption, equipment damage, or safety incidents through unauthorized controller manipulation.

🟠

Likely Case

Unauthorized access to controller configurations and logic, potentially enabling industrial espionage or preparation for future attacks.

🟢

If Mitigated

Limited impact if physical keyswitch protection is properly utilized and network segmentation prevents protocol access.

🌐 Internet-Facing: HIGH if protocols are exposed to internet, as no authentication prevents any remote attacker from exploiting.
🏢 Internal Only: HIGH for internal networks, as any internal attacker or compromised system can access these protocols without credentials.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: LIKELY
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Direct protocol communication without authentication makes exploitation straightforward for attackers with network access.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Not specified

Vendor Advisory: https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-02

Restart Required: No

Instructions:

No official patch available. Follow vendor guidance and implement compensating controls.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate Safety Manager systems in dedicated network segments with strict access controls.

Firewall Rules

all

Block external access to ports 51000/TCP and 51010/TCP at network perimeter.

🧯 If You Can't Patch

  • Implement strict network segmentation and zero-trust architecture around Safety Manager systems
  • Deploy industrial intrusion detection systems monitoring for protocol anomalies on ports 51000 and 51010

🔍 How to Verify

Check if Vulnerable:

Check if Honeywell Experion PKS Safety Manager is installed and if ports 51000/TCP or 51010/TCP are accessible.

Check Version:

Check system documentation or contact Honeywell support for version information.

Verify Fix Applied:

Verify network segmentation prevents access to affected ports and monitor for unauthorized connection attempts.

📡 Detection & Monitoring

Log Indicators:

  • Unauthorized connection attempts to ports 51000/TCP or 51010/TCP
  • Unexpected controller state changes or configuration modifications

Network Indicators:

  • Traffic to/from ports 51000/TCP or 51010/TCP from unauthorized sources
  • Protocol anomalies in Experion TCP or Safety Builder communications

SIEM Query:

source_port:51000 OR source_port:51010 OR destination_port:51000 OR destination_port:51010