CVE-2022-30310
📋 TL;DR
This vulnerability allows unauthenticated attackers to execute arbitrary system commands with root privileges on Festo Controller CECC-X-M1 devices. Attackers can exploit an HTTP endpoint that doesn't properly validate port syntax in POST requests, leading to command injection. This affects all organizations using vulnerable versions of these industrial controllers.
💻 Affected Systems
- Festo Controller CECC-X-M1 product family
📦 What is this software?
Controller Cecc X M1 Mv Firmware by Festo
Controller Cecc X M1 Mv Firmware by Festo
Controller Cecc X M1 Mv S1 Firmware by Festo
View all CVEs affecting Controller Cecc X M1 Mv S1 Firmware →
Controller Cecc X M1 Mv S1 Firmware by Festo
View all CVEs affecting Controller Cecc X M1 Mv S1 Firmware →
Controller Cecc X M1 Y Yjkp Firmware by Festo
View all CVEs affecting Controller Cecc X M1 Y Yjkp Firmware →
Controller Cecc X M1 Ys L1 Firmware by Festo
View all CVEs affecting Controller Cecc X M1 Ys L1 Firmware →
⚠️ Risk & Real-World Impact
Worst Case
Complete compromise of industrial control systems, allowing attackers to execute arbitrary commands as root, potentially disrupting manufacturing processes, stealing sensitive data, or causing physical damage.
Likely Case
Unauthorized access to controller systems, installation of malware or backdoors, data exfiltration, and potential disruption of industrial operations.
If Mitigated
Limited impact if proper network segmentation, access controls, and monitoring are in place to prevent exploitation attempts.
🎯 Exploit Status
The vulnerability requires no authentication and involves simple command injection via HTTP POST requests, making exploitation straightforward for attackers with network access.
🛠️ Fix & Mitigation
✅ Official Fix
Patch Version: Not specified in provided references
Vendor Advisory: https://cert.vde.com/en/advisories/VDE-2022-020/
Restart Required: Yes
Instructions:
1. Contact Festo support for specific patch information. 2. Apply vendor-provided firmware updates. 3. Restart affected controllers after patching. 4. Verify the fix by testing the vulnerable endpoint.
🔧 Temporary Workarounds
Network Segmentation
allIsolate Festo controllers from untrusted networks using firewalls and VLANs
Access Control Lists
allRestrict HTTP access to controller interfaces to authorized IP addresses only
🧯 If You Can't Patch
- Implement strict network segmentation to isolate controllers from all untrusted networks
- Deploy intrusion detection systems to monitor for exploitation attempts and block malicious traffic
🔍 How to Verify
Check if Vulnerable:
Test if the HTTP endpoint '/cecc-x-acknerr-request' accepts POST requests with command injection payloads in port parameters
Check Version:
Check controller firmware version through web interface or device management tools
Verify Fix Applied:
After patching, attempt to exploit the vulnerability and verify that command injection is no longer possible
📡 Detection & Monitoring
Log Indicators:
- HTTP POST requests to '/cecc-x-acknerr-request' with unusual port parameters
- System command execution from web service processes
Network Indicators:
- HTTP traffic to controller ports containing command injection patterns
- Unexpected outbound connections from controllers
SIEM Query:
source="festo_controller" AND (url="/cecc-x-acknerr-request" OR cmd="*injection*" OR port="*;*" OR port="*|*")