CVE-2022-21214

7.8 HIGH

📋 TL;DR

This vulnerability allows attackers to execute arbitrary code on affected systems by exploiting a heap-based buffer overflow. It affects specific industrial control system products from Rockwell Automation. Organizations using these products in critical infrastructure are at risk.

💻 Affected Systems

Products:
  • Rockwell Automation FactoryTalk Linx
Versions: All versions prior to 6.11
Operating Systems: Windows
Default Config Vulnerable: ⚠️ Yes
Notes: Affects FactoryTalk Linx communication software used in industrial environments.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Full system compromise leading to disruption of industrial processes, data theft, or physical damage to equipment.

🟠

Likely Case

Denial of service or limited code execution allowing attackers to pivot within the network.

🟢

If Mitigated

Limited impact if network segmentation and access controls prevent exploitation attempts.

🌐 Internet-Facing: HIGH
🏢 Internal Only: MEDIUM

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: MEDIUM

Requires network access to vulnerable service but no authentication.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Version 6.11 or later

Vendor Advisory: https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1653.html

Restart Required: Yes

Instructions:

1. Download FactoryTalk Linx version 6.11 or later from Rockwell Automation. 2. Install the update following vendor documentation. 3. Restart affected systems.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate FactoryTalk Linx systems from untrusted networks using firewalls.

Disable Unnecessary Services

windows

Turn off FactoryTalk Linx services not required for operations.

🧯 If You Can't Patch

  • Implement strict network access controls to limit connections to FactoryTalk Linx systems.
  • Monitor network traffic for unusual patterns and implement intrusion detection systems.

🔍 How to Verify

Check if Vulnerable:

Check FactoryTalk Linx version in Control Panel > Programs and Features. Versions below 6.11 are vulnerable.

Check Version:

wmic product where name="FactoryTalk Linx" get version

Verify Fix Applied:

Confirm version is 6.11 or higher after patching and test communication functionality.

📡 Detection & Monitoring

Log Indicators:

  • Unusual network connections to FactoryTalk Linx ports
  • Process crashes or unexpected restarts

Network Indicators:

  • Suspicious traffic on FactoryTalk Linx default ports (44818, 2222)

SIEM Query:

source_port=44818 OR dest_port=44818 AND (event_type="connection_attempt" OR event_type="anomaly")