CVE-2021-37184

9.8 CRITICAL

📋 TL;DR

An unauthenticated attacker can change any user's password in Siemens Industrial Edge Management systems, allowing impersonation of valid users. This affects all versions before V1.3 of the Industrial Edge Management platform.

💻 Affected Systems

Products:
  • Siemens Industrial Edge Management
Versions: All versions < V1.3
Default Config Vulnerable: ⚠️ Yes
Notes: Affects the Industrial Edge Management platform specifically; other Siemens products are not affected.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete system compromise through administrative account takeover, leading to industrial control system manipulation, data theft, or operational disruption.

🟠

Likely Case

Unauthorized access to sensitive industrial data, configuration changes, or lateral movement within the network.

🟢

If Mitigated

Limited impact if systems are isolated, monitored, and have strong authentication controls beyond the vulnerable component.

🌐 Internet-Facing: HIGH
🏢 Internal Only: HIGH

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

The vulnerability requires no authentication and can be exploited under certain circumstances as described in the advisory.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: V1.3 or later

Vendor Advisory: https://cert-portal.siemens.com/productcert/pdf/ssa-692317.pdf

Restart Required: Yes

Instructions:

1. Download Industrial Edge Management V1.3 or later from Siemens support portal. 2. Backup current configuration. 3. Apply the update following Siemens installation guide. 4. Restart the system.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate Industrial Edge Management systems from untrusted networks to prevent unauthenticated access.

Access Control Lists

all

Implement strict firewall rules to limit access to the management interface to authorized IPs only.

🧯 If You Can't Patch

  • Implement network segmentation to isolate affected systems from untrusted networks.
  • Enable detailed logging and monitoring for unauthorized password change attempts.

🔍 How to Verify

Check if Vulnerable:

Check the Industrial Edge Management version in the system settings or via CLI command 'iem-version'.

Check Version:

iem-version

Verify Fix Applied:

Confirm version is V1.3 or higher and test that unauthenticated password changes are no longer possible.

📡 Detection & Monitoring

Log Indicators:

  • Unauthenticated password change requests in application logs
  • Multiple failed login attempts followed by password reset

Network Indicators:

  • Unusual traffic to password reset endpoints from untrusted sources

SIEM Query:

source="industrial_edge" AND (event="password_change" OR event="user_modify") AND user="unauthenticated"