CVE-2021-22714

9.8 CRITICAL

📋 TL;DR

This vulnerability is a memory buffer overflow in Schneider Electric PowerLogic meters that could allow attackers to cause denial of service (reboots) or execute arbitrary code remotely. It affects ION7400, PM8000, and ION9000 series power meters. Organizations using these devices for energy monitoring and management are at risk.

💻 Affected Systems

Products:
  • PowerLogic ION7400
  • PowerLogic PM8000
  • PowerLogic ION9000
Versions: All versions prior to V3.0.0
Operating Systems: Embedded firmware
Default Config Vulnerable: ⚠️ Yes
Notes: All configurations of affected versions are vulnerable. These are industrial power monitoring devices typically deployed in electrical distribution systems.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Remote code execution allowing complete compromise of the meter, potential lateral movement to other systems, and manipulation of power monitoring data.

🟠

Likely Case

Meter reboots causing temporary loss of power monitoring data and potential disruption to energy management systems.

🟢

If Mitigated

Limited impact if meters are isolated on separate networks with strict access controls.

🌐 Internet-Facing: HIGH - If meters are directly exposed to the internet, they are vulnerable to remote exploitation.
🏢 Internal Only: HIGH - Even internally, these devices are vulnerable to network-based attacks from compromised internal systems.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: MEDIUM

The vulnerability allows remote exploitation without authentication. While no public exploit code is known, the high CVSS score suggests exploitation is feasible.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: V3.0.0 and later

Vendor Advisory: https://www.se.com/ww/en/download/document/SEVD-2021-068-02

Restart Required: Yes

Instructions:

1. Download firmware version 3.0.0 or later from Schneider Electric website. 2. Backup current configuration. 3. Upload new firmware via web interface or configuration tool. 4. Reboot meter to apply update. 5. Verify firmware version after reboot.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate power meters on separate VLANs with strict firewall rules limiting access to authorized management systems only.

Access Control Lists

all

Implement network ACLs to restrict access to meter management interfaces to specific IP addresses.

🧯 If You Can't Patch

  • Segment meters on isolated networks with no internet access
  • Implement strict firewall rules allowing only necessary management traffic from authorized sources

🔍 How to Verify

Check if Vulnerable:

Check firmware version via web interface or configuration tool. If version is below 3.0.0, the device is vulnerable.

Check Version:

Check via web interface at http://[meter-ip]/ or using Schneider Electric configuration tools

Verify Fix Applied:

After updating, verify firmware version shows 3.0.0 or higher and confirm normal operation of power monitoring functions.

📡 Detection & Monitoring

Log Indicators:

  • Unexpected meter reboots
  • Failed login attempts to meter interface
  • Unusual network connections to meter ports

Network Indicators:

  • Unusual traffic patterns to meter management ports (typically 80, 443, 502)
  • Traffic from unexpected source IPs to meter

SIEM Query:

source_ip=* AND dest_ip=[meter_ip] AND (port=80 OR port=443 OR port=502) AND NOT source_ip IN [authorized_ips]

🔗 References

📤 Share & Export