CVE-2021-22713
📋 TL;DR
This vulnerability is a memory buffer overflow in Schneider Electric PowerLogic ION series power meters that could allow an attacker to cause denial of service by rebooting the device. It affects multiple ION meter models running vulnerable firmware versions. Organizations using these industrial power monitoring devices are at risk.
💻 Affected Systems
- PowerLogic ION8650
- ION8800
- ION7650
- ION7700/73xx
- ION83xx/84xx/85xx/8600
📦 What is this software?
Ion7650 Firmware by Schneider Electric
Powerlogic Ion7300 Firmware by Schneider Electric
Powerlogic Ion7550 Firmware by Schneider Electric
Powerlogic Ion7550 Firmware by Schneider Electric
Powerlogic Ion7650 Firmware by Schneider Electric
Powerlogic Ion7700 Firmware by Schneider Electric
Powerlogic Ion8300 Firmware by Schneider Electric
Powerlogic Ion8400 Firmware by Schneider Electric
Powerlogic Ion8500 Firmware by Schneider Electric
Powerlogic Ion8600 Firmware by Schneider Electric
Powerlogic Ion8650 Firmware by Schneider Electric
Powerlogic Ion8800 Firmware by Schneider Electric
⚠️ Risk & Real-World Impact
Worst Case
Persistent denial of service through repeated reboots, potentially disrupting power monitoring and control systems in critical infrastructure environments.
Likely Case
Temporary disruption of power monitoring data collection and potential loss of historical data during reboot cycles.
If Mitigated
Isolated incident with minimal operational impact if meters are properly segmented and monitored.
🎯 Exploit Status
The vulnerability requires network access to the meter's communication interfaces but does not require authentication.
🛠️ Fix & Mitigation
✅ Official Fix
Patch Version: Firmware versions specified in SEVD-2021-068-03
Vendor Advisory: https://www.se.com/ww/en/download/document/SEVD-2021-068-03
Restart Required: Yes
Instructions:
1. Download updated firmware from Schneider Electric portal. 2. Backup current configuration. 3. Apply firmware update via appropriate interface (Ethernet, serial). 4. Verify successful update and restore configuration if needed.
🔧 Temporary Workarounds
Network segmentation
allIsolate ION meters on dedicated VLANs with strict firewall rules limiting access to authorized management systems only.
Access control restrictions
allImplement strict network access controls to prevent unauthorized systems from communicating with ION meter interfaces.
🧯 If You Can't Patch
- Implement strict network segmentation to isolate ION meters from general network traffic
- Deploy intrusion detection systems to monitor for anomalous traffic patterns to ION meter interfaces
🔍 How to Verify
Check if Vulnerable:
Check firmware version via meter's web interface or communication protocol and compare against vulnerable versions in SEVD-2021-068-03.
Check Version:
Use ION Setup software or web interface to query device firmware version.
Verify Fix Applied:
Confirm firmware version matches patched versions listed in vendor advisory and test meter functionality.
📡 Detection & Monitoring
Log Indicators:
- Unexpected meter reboots
- Communication timeouts with meters
- Failed authentication attempts to meter interfaces
Network Indicators:
- Unusual traffic patterns to meter IP addresses
- Protocol anomalies in ION communication
SIEM Query:
source="network_firewall" dest_ip="meter_subnet" AND (protocol_anomaly OR connection_attempts > threshold)