CVE-2020-28212

9.8 CRITICAL

📋 TL;DR

This vulnerability allows attackers to perform brute force attacks against the PLC Simulator in EcoStruxure Control Expert (Unity Pro) via Modbus protocol, potentially leading to unauthorized command execution. All versions of the software are affected, primarily impacting industrial control systems using Schneider Electric's PLC programming environment.

💻 Affected Systems

Products:
  • EcoStruxure Control Expert
  • Unity Pro
Versions: all versions
Operating Systems: Windows
Default Config Vulnerable: ⚠️ Yes
Notes: Affects PLC Simulator component specifically; requires Modbus access to the simulator service.

📦 What is this software?

⚠️ Manual Verification Required

This CVE does not have specific version information in our database, so automatic vulnerability detection cannot determine if your system is affected.

Why? The CVE database entry doesn't specify which versions are vulnerable (no version ranges provided by the vendor/NVD).

🔒 Custom verification scripts are available for registered users. Sign up free to download automated test scripts.

Recommended Actions:
  1. Review the CVE details at NVD
  2. Check vendor security advisories for your specific version
  3. Test if the vulnerability is exploitable in your environment
  4. Consider updating to the latest version as a precaution

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete compromise of PLC simulator allowing unauthorized command execution, potential manipulation of simulated industrial processes, and foothold for attacking connected systems.

🟠

Likely Case

Unauthorized access to PLC simulator functions, manipulation of simulation parameters, and potential data exfiltration from the simulation environment.

🟢

If Mitigated

Limited impact with proper network segmentation and authentication controls, though simulation integrity could still be compromised.

🌐 Internet-Facing: HIGH
🏢 Internal Only: HIGH

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: LIKELY
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Brute force attacks via Modbus protocol are well-understood and tools exist for Modbus enumeration/attacks.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Not version-specific - requires configuration changes

Vendor Advisory: https://www.se.com/ww/en/download/document/SEVD-2020-315-07

Restart Required: No

Instructions:

1. Download and review SEVD-2020-315-07 advisory. 2. Implement authentication rate limiting on Modbus interface. 3. Configure network access controls. 4. Apply principle of least privilege to simulator access.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate PLC Simulator from untrusted networks and implement strict firewall rules for Modbus traffic.

Authentication Hardening

windows

Implement account lockout policies and strong authentication mechanisms for simulator access.

🧯 If You Can't Patch

  • Implement network-level rate limiting for Modbus traffic using firewalls or network security devices.
  • Deploy intrusion detection systems monitoring for Modbus brute force patterns and anomalous command sequences.

🔍 How to Verify

Check if Vulnerable:

Test if Modbus interface accepts unlimited authentication attempts without lockout mechanisms.

Check Version:

Check Control Expert/Unity Pro version in Help > About menu.

Verify Fix Applied:

Verify authentication rate limiting is enforced and Modbus access is properly restricted.

📡 Detection & Monitoring

Log Indicators:

  • Multiple failed authentication attempts from single source
  • Unusual Modbus command sequences
  • Authentication bypass events

Network Indicators:

  • High volume of Modbus authentication packets
  • Brute force patterns on TCP port 502
  • Unauthorized Modbus function codes

SIEM Query:

source_port:502 AND (event_type:auth_failure OR event_type:modbus_command) | stats count by src_ip dest_ip

🔗 References