CVE-2020-15786

9.8 CRITICAL

📋 TL;DR

This vulnerability allows remote attackers to perform brute-force attacks against SIMATIC HMI panels due to insufficient authentication attempt blocking. Attackers could discover user passwords and gain access to the Sm@rt Server. Affected devices include various SIMATIC HMI panel models running vulnerable firmware versions.

💻 Affected Systems

Products:
  • SIMATIC HMI Basic Panels 2nd Generation
  • SIMATIC HMI Comfort Panels
  • SIMATIC HMI Mobile Panels
  • SIMATIC HMI Unified Comfort Panels
Versions: All versions < V16 for Basic Panels, all versions <= V16 for others
Operating Systems: Siemens HMI firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Includes SIPLUS variants. Affects Sm@rt Server authentication mechanism.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Full compromise of HMI panels allowing attackers to manipulate industrial processes, steal sensitive data, or disrupt operations.

🟠

Likely Case

Unauthorized access to HMI interfaces leading to data theft, configuration changes, or operational disruption.

🟢

If Mitigated

Limited impact with proper network segmentation and monitoring, though authentication bypass remains possible.

🌐 Internet-Facing: HIGH - Directly exposed panels can be brute-forced from anywhere on the internet.
🏢 Internal Only: HIGH - Even internally, attackers with network access can exploit this vulnerability.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: LIKELY
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Brute-force attacks require no authentication and use standard tools. Attack complexity is minimal.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: V16 or later

Vendor Advisory: https://cert-portal.siemens.com/productcert/pdf/ssa-542525.pdf

Restart Required: Yes

Instructions:

1. Download firmware update V16 or later from Siemens support portal. 2. Backup current configuration. 3. Apply firmware update following Siemens documentation. 4. Restart affected panels. 5. Verify successful update.

🔧 Temporary Workarounds

Network segmentation and access control

all

Restrict network access to HMI panels using firewalls and VLANs to limit exposure.

Strong password policy

all

Implement complex passwords to increase brute-force resistance time.

🧯 If You Can't Patch

  • Implement network-level rate limiting for authentication attempts
  • Deploy intrusion detection systems to monitor for brute-force patterns

🔍 How to Verify

Check if Vulnerable:

Check firmware version on HMI panel via control panel or Siemens TIA Portal.

Check Version:

Check via Siemens TIA Portal or panel display settings.

Verify Fix Applied:

Confirm firmware version is V16 or later and test authentication attempt blocking.

📡 Detection & Monitoring

Log Indicators:

  • Multiple failed authentication attempts from single IP
  • Successful logins after many failures

Network Indicators:

  • High volume of authentication requests to HMI panels
  • Traffic patterns matching brute-force tools

SIEM Query:

source_ip=* AND (event_type="authentication_failure" OR event_type="login_failed") COUNT > 10 WITHIN 5min

🔗 References

📤 Share & Export