CVE-2018-7846

9.8 CRITICAL

📋 TL;DR

This vulnerability allows attackers to bypass authentication on Schneider Electric Modicon PLCs via brute force attacks on the Modbus protocol. It affects all versions of Modicon M580, M340, Quantum, and Premium controllers, potentially granting unauthorized access to industrial control systems.

💻 Affected Systems

Products:
  • Modicon M580
  • Modicon M340
  • Modicon Quantum
  • Modicon Premium
Versions: All versions
Operating Systems: PLC firmware
Default Config Vulnerable: ⚠️ Yes
Notes: All affected controllers are vulnerable in default configurations when using Modbus protocol.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete compromise of industrial control systems leading to physical damage, production shutdown, or safety incidents.

🟠

Likely Case

Unauthorized access to PLCs allowing manipulation of industrial processes, data theft, or denial of service.

🟢

If Mitigated

Limited impact with proper network segmentation and authentication controls in place.

🌐 Internet-Facing: HIGH - Direct internet exposure makes brute force attacks trivial.
🏢 Internal Only: MEDIUM - Internal attackers or compromised systems could still exploit this vulnerability.

🎯 Exploit Status

Public PoC: ⚠️ Yes
Weaponized: LIKELY
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Brute force attacks on Modbus protocol are well-documented and tools are publicly available.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Refer to Schneider Electric security updates

Vendor Advisory: https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/

Restart Required: Yes

Instructions:

1. Download firmware updates from Schneider Electric. 2. Apply updates following vendor instructions. 3. Restart affected controllers. 4. Verify patch application.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate PLCs from untrusted networks using firewalls and VLANs.

Modbus Access Control

all

Restrict Modbus protocol access to authorized IP addresses only.

🧯 If You Can't Patch

  • Implement strict network segmentation and firewall rules to block unauthorized Modbus access.
  • Deploy intrusion detection systems to monitor for brute force attempts on Modbus ports.

🔍 How to Verify

Check if Vulnerable:

Check if affected Schneider Electric PLC models are exposed to Modbus protocol without authentication controls.

Check Version:

Use Schneider Electric engineering software to check PLC firmware version.

Verify Fix Applied:

Verify firmware version matches patched versions from Schneider Electric advisory.

📡 Detection & Monitoring

Log Indicators:

  • Multiple failed authentication attempts on Modbus ports
  • Unusual Modbus traffic patterns

Network Indicators:

  • Brute force attempts on TCP port 502 (Modbus)
  • Unauthorized IP addresses accessing Modbus services

SIEM Query:

source_port:502 AND (event_type:authentication_failure OR event_count > threshold)

🔗 References

📤 Share & Export