CVE-2025-9464

7.5 HIGH

📋 TL;DR

A denial-of-service vulnerability in ArmorStart LT industrial motor controllers allows attackers to crash the CIP port by sending specially crafted packets. This affects industrial control systems using vulnerable ArmorStart LT devices, potentially disrupting motor operations and production processes.

💻 Affected Systems

Products:
  • Rockwell Automation ArmorStart LT
Versions: All versions prior to the fix
Operating Systems: Embedded firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Only affects devices with CIP connectivity enabled. Devices in standalone mode without network connectivity are not vulnerable.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete loss of motor control in critical industrial processes, leading to production shutdowns, equipment damage, or safety incidents.

🟠

Likely Case

Temporary disruption of motor operations requiring manual intervention and device restart, causing production delays.

🟢

If Mitigated

Isolated impact on individual motor controllers with minimal production disruption if proper network segmentation is in place.

🌐 Internet-Facing: LOW - Industrial control systems should never be directly internet-facing. If exposed, risk becomes HIGH.
🏢 Internal Only: MEDIUM - Attackers with network access to the industrial control network could disrupt operations.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Vulnerability discovered through fuzzing. Exploitation requires network access to the CIP port but no authentication.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Refer to Rockwell Automation advisory SD1768 for specific firmware versions

Vendor Advisory: https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1768.html

Restart Required: Yes

Instructions:

1. Download firmware update from Rockwell Automation website. 2. Connect to device using appropriate programming software. 3. Upload new firmware. 4. Restart device. 5. Verify firmware version.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate ArmorStart LT devices in separate VLANs with strict firewall rules limiting CIP traffic to authorized sources only.

Disable Unnecessary CIP Services

all

Configure devices to disable CIP services not required for operation.

🧯 If You Can't Patch

  • Implement strict network access controls allowing only trusted devices to communicate with ArmorStart LT CIP ports
  • Monitor network traffic for abnormal CIP packet patterns and implement automated alerting

🔍 How to Verify

Check if Vulnerable:

Check firmware version against Rockwell Automation advisory SD1768. Devices with firmware versions listed as vulnerable are affected.

Check Version:

Use Rockwell Automation programming software (Studio 5000 Logix Designer or similar) to read device firmware version.

Verify Fix Applied:

Verify firmware version matches patched version specified in Rockwell Automation advisory. Test CIP connectivity and functionality.

📡 Detection & Monitoring

Log Indicators:

  • Device restart logs
  • CIP communication failure logs
  • Network timeout errors

Network Indicators:

  • Unusual CIP packet patterns
  • Multiple malformed CIP requests to port 44818
  • Sudden cessation of normal CIP traffic

SIEM Query:

source_port:44818 AND (packet_size:>1500 OR protocol_anomaly:true)