CVE-2025-59301

4.0 MEDIUM

📋 TL;DR

Delta Electronics DVP15MC11T programmable logic controllers lack proper validation of Modbus/TCP packets, allowing specially crafted packets to cause denial of service. This affects industrial control systems using these specific PLCs. The vulnerability requires network access to the Modbus/TCP port.

💻 Affected Systems

Products:
  • Delta Electronics DVP15MC11T
Versions: All versions prior to firmware update
Operating Systems: Embedded firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Only affects systems with Modbus/TCP enabled and accessible.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete PLC unresponsiveness requiring physical reset or power cycle, disrupting industrial processes and potentially causing production downtime.

🟠

Likely Case

Temporary PLC unresponsiveness or communication disruption until device is restarted or malicious traffic stops.

🟢

If Mitigated

No impact if proper network segmentation and access controls prevent unauthorized Modbus/TCP access.

🌐 Internet-Facing: HIGH if Modbus/TCP port is exposed to internet without proper controls.
🏢 Internal Only: MEDIUM as internal attackers or compromised systems could exploit this to disrupt operations.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires sending malformed Modbus/TCP packets to port 502. No authentication needed.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Refer to Delta Electronics advisory for specific firmware version

Vendor Advisory: https://filecenter.deltaww.com/news/download/doc/Delta-PCSA-2025-00020_DVP15MC11T%20Modbus%20TCP%20DoS%20Vulnerability.pdf

Restart Required: Yes

Instructions:

1. Download firmware update from Delta Electronics support portal. 2. Connect to PLC via programming software. 3. Upload new firmware. 4. Restart PLC.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate PLCs in separate network segment with strict firewall rules

Access Control Lists

all

Restrict Modbus/TCP access to authorized IP addresses only

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate PLCs from untrusted networks
  • Deploy intrusion detection systems to monitor for malformed Modbus/TCP packets

🔍 How to Verify

Check if Vulnerable:

Check if DVP15MC11T is running vulnerable firmware version via Delta programming software

Check Version:

Use Delta DVPSoft or ISPSoft programming software to read PLC firmware version

Verify Fix Applied:

Verify firmware version matches patched version in vendor advisory

📡 Detection & Monitoring

Log Indicators:

  • PLC communication errors
  • Unexpected PLC restarts
  • Modbus protocol violations

Network Indicators:

  • Malformed Modbus/TCP packets to port 502
  • Unusual traffic patterns to PLCs

SIEM Query:

source_port:502 AND (packet_size:>300 OR protocol_violation:true)