CVE-2025-48019

6.5 MEDIUM

📋 TL;DR

A vulnerability in Yokogawa's Vnet/IP Interface Package allows remote attackers to cause denial of service by sending maliciously crafted packets, which can terminate the Vnet/IP software stack process. This affects industrial control systems using CENTUM VP R6 and R7 with the vulnerable interface package. Organizations using these Yokogawa industrial automation products are at risk.

💻 Affected Systems

Products:
  • Vnet/IP Interface Package for CENTUM VP R6 VP6C3300
  • Vnet/IP Interface Package for CENTUM VP R7 VP7C3300
Versions: R1.07.00 and earlier
Operating Systems: Windows-based industrial control systems running CENTUM VP
Default Config Vulnerable: ⚠️ Yes
Notes: Affects specific interface packages for Yokogawa's CENTUM VP distributed control system used in industrial automation.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete disruption of Vnet/IP communication in industrial control systems, potentially affecting process monitoring and control in critical infrastructure environments.

🟠

Likely Case

Service interruption requiring manual restart of affected Vnet/IP components, causing temporary loss of process visibility and control.

🟢

If Mitigated

Isolated impact limited to specific interface components with redundant systems maintaining overall process control.

🌐 Internet-Facing: LOW - Industrial control systems should not be directly internet-facing, but risk increases if improperly exposed.
🏢 Internal Only: MEDIUM - Requires network access to affected systems, but industrial networks often have flat architectures that could facilitate lateral movement.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: MEDIUM

Exploitation requires crafting specific network packets but does not require authentication. The CWE-617 indicates a reachable assertion vulnerability.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Versions newer than R1.07.00

Vendor Advisory: https://web-material3.yokogawa.com/1/39281/files/YSAR-26-0002-E.pdf

Restart Required: Yes

Instructions:

1. Download updated Vnet/IP Interface Package from Yokogawa support portal. 2. Follow vendor installation procedures for CENTUM VP systems. 3. Apply to all affected systems. 4. Restart Vnet/IP services or affected systems as required.

🔧 Temporary Workarounds

Network segmentation and filtering

all

Restrict network access to Vnet/IP interfaces using firewalls and network segmentation

Protocol filtering

all

Implement network monitoring to detect and block malformed Vnet/IP packets

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate Vnet/IP interfaces from untrusted networks
  • Deploy intrusion detection systems to monitor for malformed packet patterns targeting Vnet/IP services

🔍 How to Verify

Check if Vulnerable:

Check Vnet/IP Interface Package version in CENTUM VP system configuration or using vendor-provided diagnostic tools

Check Version:

Use Yokogawa CENTUM VP system utilities or check package installation details in control system configuration

Verify Fix Applied:

Verify installed version is newer than R1.07.00 and test Vnet/IP communication functionality

📡 Detection & Monitoring

Log Indicators:

  • Unexpected termination of Vnet/IP processes
  • Connection resets or timeouts in Vnet/IP communication logs
  • System event logs showing service crashes

Network Indicators:

  • Unusual packet patterns to Vnet/IP ports (typically UDP 1200)
  • Multiple connection attempts to Vnet/IP services from single sources

SIEM Query:

source="industrial_control_logs" AND (process_name="VnetIP" OR service_name="Vnet/IP") AND (event_type="crash" OR event_type="termination")