CVE-2025-40757

5.3 MEDIUM

📋 TL;DR

This vulnerability allows attackers to download encrypted database files containing passwords from Siemens building automation controllers without authentication. Affected devices include Siemens APOGEE PXC and TALON TC series controllers running all versions when connected to networks.

💻 Affected Systems

Products:
  • APOGEE PXC Series (BACnet)
  • APOGEE PXC Series (P2 Ethernet)
  • TALON TC Series (BACnet)
Versions: All versions
Operating Systems: Embedded controller firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Devices are vulnerable when connected to any network segment accessible to attackers. No special configuration required for exploitation.

⚠️ Manual Verification Required

This CVE does not have specific version information in our database, so automatic vulnerability detection cannot determine if your system is affected.

Why? The CVE database entry doesn't specify which versions are vulnerable (no version ranges provided by the vendor/NVD).

🔒 Custom verification scripts are available for registered users. Sign up free to download automated test scripts.

Recommended Actions:
  1. Review the CVE details at NVD
  2. Check vendor security advisories for your specific version
  3. Test if the vulnerability is exploitable in your environment
  4. Consider updating to the latest version as a precaution

⚠️ Risk & Real-World Impact

🔴

Worst Case

Attackers obtain encrypted password databases, potentially enabling credential cracking and subsequent lateral movement to compromise building automation systems, HVAC controls, or physical security systems.

🟠

Likely Case

Attackers download encrypted password files and attempt offline cracking, potentially gaining access to building management systems and sensitive operational data.

🟢

If Mitigated

With proper network segmentation and access controls, attackers cannot reach vulnerable devices, limiting exposure to isolated network segments.

🌐 Internet-Facing: HIGH
🏢 Internal Only: MEDIUM

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires network access to vulnerable devices but no authentication or special tools.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Contact Siemens for specific firmware updates

Vendor Advisory: https://cert-portal.siemens.com/productcert/html/ssa-916339.html

Restart Required: Yes

Instructions:

1. Contact Siemens support for firmware updates. 2. Download appropriate firmware for your controller model. 3. Apply firmware update following Siemens documentation. 4. Verify update completion and functionality.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate building automation controllers on separate VLANs with strict firewall rules

Access Control Lists

all

Implement network ACLs to restrict access to BACnet and P2 Ethernet ports (typically 47808 for BACnet)

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate building automation systems from general corporate networks
  • Deploy intrusion detection systems to monitor for unauthorized access attempts to controller ports

🔍 How to Verify

Check if Vulnerable:

Check if device models match affected products list and are accessible on network without authentication

Check Version:

Consult Siemens documentation for device-specific version checking commands

Verify Fix Applied:

Verify firmware version against Siemens patched versions and test that database files are no longer accessible without authentication

📡 Detection & Monitoring

Log Indicators:

  • Unauthorized access attempts to controller IP addresses
  • Unexpected file download activity from controller devices

Network Indicators:

  • Unusual traffic to BACnet port 47808 or P2 Ethernet ports from unauthorized sources
  • Database file transfers from controller IPs

SIEM Query:

source_ip NOT IN (authorized_ips) AND dest_port IN (47808, other_controller_ports)

🔗 References