CVE-2025-30031

8.8 HIGH

📋 TL;DR

This SQL injection vulnerability in TeleControl Server Basic allows authenticated remote attackers to bypass authorization controls, read/write to the database, and execute code with NetworkService permissions. All versions before V3.1.2.2 are affected. Attackers need access to port 8000 on systems running vulnerable versions.

💻 Affected Systems

Products:
  • TeleControl Server Basic
Versions: All versions < V3.1.2.2
Operating Systems: Windows (based on NT AUTHORITY\NetworkService reference)
Default Config Vulnerable: ⚠️ Yes
Notes: Requires authentication and access to port 8000. NetworkService permissions indicate Windows environment.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete system compromise with NetworkService privileges leading to lateral movement, data exfiltration, and persistent backdoor installation.

🟠

Likely Case

Database manipulation, credential theft, and unauthorized access to control systems data.

🟢

If Mitigated

Limited impact due to network segmentation and strict access controls preventing port 8000 exposure.

🌐 Internet-Facing: HIGH - Port 8000 exposed to internet allows authenticated attackers to exploit SQL injection for full system compromise.
🏢 Internal Only: HIGH - Even internal attackers with authentication can exploit this for privilege escalation and code execution.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ✅ No
Complexity: LOW

SQL injection vulnerabilities are typically easy to exploit once identified. Requires authenticated access to port 8000.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: V3.1.2.2

Vendor Advisory: https://cert-portal.siemens.com/productcert/html/ssa-443402.html

Restart Required: Yes

Instructions:

1. Download V3.1.2.2 or later from Siemens official sources. 2. Backup configuration and data. 3. Stop TeleControl Server Basic service. 4. Install the update. 5. Restart the service and verify functionality.

🔧 Temporary Workarounds

Network Segmentation

windows

Restrict access to port 8000/TCP to only trusted management networks

Windows Firewall: New-NetFirewallRule -DisplayName "Block TeleControl Port 8000" -Direction Inbound -LocalPort 8000 -Protocol TCP -Action Block
netsh advfirewall firewall add rule name="Block TeleControl Port 8000" dir=in action=block protocol=TCP localport=8000

Authentication Hardening

all

Implement strong authentication policies and monitor for suspicious login attempts

🧯 If You Can't Patch

  • Implement strict network access controls to limit port 8000 exposure to minimal necessary sources
  • Deploy web application firewall (WAF) with SQL injection protection rules in front of the service

🔍 How to Verify

Check if Vulnerable:

Check TeleControl Server Basic version in application interface or registry: HKEY_LOCAL_MACHINE\SOFTWARE\Siemens\TeleControl Server Basic\Version

Check Version:

reg query "HKLM\SOFTWARE\Siemens\TeleControl Server Basic" /v Version

Verify Fix Applied:

Verify version is V3.1.2.2 or later and test UpdateUsers functionality with SQL injection test payloads

📡 Detection & Monitoring

Log Indicators:

  • Unusual SQL queries in application logs
  • Multiple failed authentication attempts followed by UpdateUsers access
  • Unexpected process execution with NetworkService context

Network Indicators:

  • SQL injection patterns in traffic to port 8000
  • Unusual database queries from TeleControl Server process
  • Unexpected outbound connections from NetworkService account

SIEM Query:

source="telecontrol_logs" AND ("UpdateUsers" AND ("UNION" OR "SELECT" OR "INSERT" OR "DELETE" OR "--" OR "' OR"))

🔗 References

📤 Share & Export