CVE-2025-15103

8.1 HIGH

📋 TL;DR

This vulnerability in Delta Electronics DVP-12SE11T PLC allows attackers to bypass authentication by obtaining partial password information through improper error messages. It affects organizations using these industrial control systems in manufacturing, energy, and infrastructure sectors.

💻 Affected Systems

Products:
  • Delta Electronics DVP-12SE11T
Versions: All versions prior to firmware update addressing CVE-2025-15103
Operating Systems: Embedded firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Affects the PLC's web interface and programming software authentication mechanisms.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Full compromise of industrial control system allowing unauthorized control of physical processes, production disruption, or safety system manipulation.

🟠

Likely Case

Unauthorized access to PLC configuration and logic, enabling monitoring of industrial processes or modification of control parameters.

🟢

If Mitigated

Limited impact if system is isolated in air-gapped network with strict access controls and monitoring.

🌐 Internet-Facing: HIGH - If exposed to internet, attackers can remotely bypass authentication and gain control.
🏢 Internal Only: MEDIUM - Internal attackers or compromised internal systems can exploit this vulnerability.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires network access to the PLC interface but no authentication credentials.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Check Delta Electronics advisory for specific firmware version

Vendor Advisory: https://filecenter.deltaww.com/news/download/doc/Delta-PCSA-2025-00022_DVP-12SE11T%20Multiple%20Vulnerabilities.pdf

Restart Required: Yes

Instructions:

1. Download latest firmware from Delta Electronics support portal. 2. Backup current configuration. 3. Apply firmware update via programming software. 4. Restart PLC. 5. Verify authentication mechanisms.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate PLCs in separate network segments with strict firewall rules.

Access Control Lists

all

Implement IP-based restrictions to limit access to PLC management interfaces.

🧯 If You Can't Patch

  • Implement strict network segmentation and zero-trust architecture around PLCs
  • Enable detailed logging and monitoring for authentication attempts and configuration changes

🔍 How to Verify

Check if Vulnerable:

Test authentication interface for password disclosure in error messages or attempt unauthorized access.

Check Version:

Check firmware version via PLC programming software or web interface.

Verify Fix Applied:

Verify authentication properly rejects invalid credentials without information disclosure and test access controls.

📡 Detection & Monitoring

Log Indicators:

  • Multiple failed authentication attempts followed by successful access
  • Authentication error messages containing password information
  • Configuration changes from unauthorized IP addresses

Network Indicators:

  • Unauthorized access to PLC management ports (typically 502/TCP Modbus, 80/443 HTTP)
  • Traffic patterns indicating authentication bypass attempts

SIEM Query:

source="plc_logs" AND (event_type="auth_failure" OR event_type="config_change") AND src_ip NOT IN allowed_ips

🔗 References