CVE-2024-6918

7.5 HIGH

📋 TL;DR

A buffer overflow vulnerability in Accutech Manager allows attackers to crash the service by sending specially crafted requests to port 2536/TCP. This affects systems running vulnerable versions of Schneider Electric's Accutech Manager software. The vulnerability could potentially lead to denial of service or remote code execution.

💻 Affected Systems

Products:
  • Schneider Electric Accutech Manager
Versions: All versions prior to the patched version (specific version not provided in CVE description)
Operating Systems: Windows (based on typical Accutech Manager deployment)
Default Config Vulnerable: ⚠️ Yes
Notes: Vulnerability exists in default configuration when Accutech Manager is running and listening on port 2536/TCP.

⚠️ Manual Verification Required

This CVE does not have specific version information in our database, so automatic vulnerability detection cannot determine if your system is affected.

Why? The CVE database entry doesn't specify which versions are vulnerable (no version ranges provided by the vendor/NVD).

🔒 Custom verification scripts are available for registered users. Sign up free to download automated test scripts.

Recommended Actions:
  1. Review the CVE details at NVD
  2. Check vendor security advisories for your specific version
  3. Test if the vulnerability is exploitable in your environment
  4. Consider updating to the latest version as a precaution

⚠️ Risk & Real-World Impact

🔴

Worst Case

Remote code execution leading to complete system compromise, data theft, or lateral movement within the network.

🟠

Likely Case

Denial of service causing Accutech Manager to crash, disrupting industrial monitoring and control operations.

🟢

If Mitigated

Limited impact with proper network segmentation and access controls preventing exploitation attempts.

🌐 Internet-Facing: HIGH - Port 2536/TCP exposed to internet would allow direct exploitation attempts from anywhere.
🏢 Internal Only: MEDIUM - Requires internal network access but could be exploited by compromised internal systems or malicious insiders.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires sending specially crafted network packets to port 2536/TCP, which is relatively straightforward for attackers with network access.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Not specified in CVE description - check vendor advisory for specific version

Vendor Advisory: https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2024-226-01&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2024-226-01.pdf

Restart Required: Yes

Instructions:

1. Download the patch from Schneider Electric's security advisory. 2. Stop the Accutech Manager service. 3. Apply the patch according to vendor instructions. 4. Restart the Accutech Manager service. 5. Verify the service is running correctly.

🔧 Temporary Workarounds

Network Access Control

all

Restrict access to port 2536/TCP using firewall rules to only allow connections from authorized systems.

# Windows Firewall: New-NetFirewallRule -DisplayName "Block Accutech Port" -Direction Inbound -LocalPort 2536 -Protocol TCP -Action Block
# Linux iptables: iptables -A INPUT -p tcp --dport 2536 -j DROP

Service Disablement

windows

Temporarily disable the Accutech Manager service if not critically needed while awaiting patch deployment.

# Windows: sc stop "Accutech Manager"
# Windows: sc config "Accutech Manager" start= disabled

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate Accutech Manager systems from untrusted networks
  • Deploy intrusion detection/prevention systems to monitor and block exploitation attempts on port 2536/TCP

🔍 How to Verify

Check if Vulnerable:

Check if Accutech Manager is running and listening on port 2536/TCP using netstat or similar tools: netstat -an | findstr :2536 (Windows) or netstat -tlnp | grep :2536 (Linux)

Check Version:

Check the software version through Accutech Manager's about dialog or installation properties.

Verify Fix Applied:

Verify the patched version is installed by checking the software version in Accutech Manager interface or installation directory.

📡 Detection & Monitoring

Log Indicators:

  • Accutech Manager service crash logs
  • Unexpected termination of Accutech Manager process
  • Error messages related to buffer overflow or memory corruption

Network Indicators:

  • Unusual traffic patterns to port 2536/TCP
  • Multiple connection attempts to port 2536 from single source
  • Malformed packets sent to port 2536

SIEM Query:

source="accutech.log" AND ("crash" OR "buffer overflow" OR "access violation") OR destination_port=2536 AND (packet_size>normal OR malformed_packet=true)

🔗 References