CVE-2024-54089

7.5 HIGH

📋 TL;DR

This vulnerability affects Siemens APOGEE PXC and TALON TC building automation controllers using weak hard-coded encryption keys. Attackers can decrypt passwords from ciphertext, potentially gaining unauthorized access to building control systems. All versions of these BACnet and P2 Ethernet devices are affected.

💻 Affected Systems

Products:
  • APOGEE PXC Series (BACnet)
  • APOGEE PXC Series (P2 Ethernet)
  • TALON TC Series (BACnet)
Versions: All versions
Operating Systems: Embedded firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Affects all configurations using the vulnerable encryption mechanism.

⚠️ Manual Verification Required

This CVE does not have specific version information in our database, so automatic vulnerability detection cannot determine if your system is affected.

Why? The CVE database entry doesn't specify which versions are vulnerable (no version ranges provided by the vendor/NVD).

🔒 Custom verification scripts are available for registered users. Sign up free to download automated test scripts.

Recommended Actions:
  1. Review the CVE details at NVD
  2. Check vendor security advisories for your specific version
  3. Test if the vulnerability is exploitable in your environment
  4. Consider updating to the latest version as a precaution

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete compromise of building automation systems allowing attackers to manipulate HVAC, lighting, security systems, or cause physical damage to equipment.

🟠

Likely Case

Unauthorized access to building control networks, credential theft, and potential lateral movement to other systems.

🟢

If Mitigated

Limited impact if devices are isolated in segmented networks with strong access controls and monitoring.

🌐 Internet-Facing: HIGH
🏢 Internal Only: MEDIUM

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ✅ No
Complexity: LOW

Exploitation requires network access to affected devices and knowledge of the weak encryption mechanism.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Contact Siemens for specific firmware updates

Vendor Advisory: https://cert-portal.siemens.com/productcert/html/ssa-615116.html

Restart Required: Yes

Instructions:

1. Review Siemens advisory SSA-615116
2. Contact Siemens support for firmware updates
3. Schedule maintenance window for updates
4. Apply firmware updates to all affected devices
5. Verify encryption mechanisms are updated

🔧 Temporary Workarounds

Network segmentation

all

Isolate affected devices in separate VLANs with strict firewall rules

Access control hardening

all

Implement strong authentication and limit administrative access to trusted networks only

🧯 If You Can't Patch

  • Segment affected devices in isolated networks with no internet access
  • Implement network monitoring and intrusion detection for anomalous access patterns

🔍 How to Verify

Check if Vulnerable:

Check device model and firmware version against Siemens advisory SSA-615116

Check Version:

Consult device documentation or Siemens support for version checking commands

Verify Fix Applied:

Verify firmware has been updated to version provided by Siemens and test encryption functionality

📡 Detection & Monitoring

Log Indicators:

  • Multiple failed authentication attempts
  • Unusual administrative access patterns
  • Configuration changes from unexpected sources

Network Indicators:

  • Unusual BACnet or P2 Ethernet traffic patterns
  • Connection attempts to building automation controllers from unauthorized networks

SIEM Query:

source_ip IN (building_automation_subnets) AND (protocol:BACnet OR protocol:P2) AND (event_type:auth_failure OR event_type:config_change)

🔗 References