CVE-2024-50956

6.5 MEDIUM

📋 TL;DR

A buffer overflow vulnerability in the RecvSocketData function of Inovance AM400 series PLCs allows attackers to cause denial of service or execute arbitrary code via specially crafted Modbus messages. This affects industrial control systems using specific versions of Inovance HCPLC_AM401, AM402, and AM403 controllers. Organizations using these PLCs in industrial environments are at risk.

💻 Affected Systems

Products:
  • Inovance HCPLC_AM401-CPU1608TPTN
  • Inovance HCPLC_AM402-CPU1608TPTN
  • Inovance HCPLC_AM403-CPU1608TN
Versions: 21.38.0.0, 41.38.0.0, 81.38.0.0 respectively
Operating Systems: PLC firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Affects Modbus TCP communication on default port 502. All configurations using these firmware versions are vulnerable.

⚠️ Manual Verification Required

This CVE does not have specific version information in our database, so automatic vulnerability detection cannot determine if your system is affected.

Why? The CVE database entry doesn't specify which versions are vulnerable (no version ranges provided by the vendor/NVD).

🔒 Custom verification scripts are available for registered users. Sign up free to download automated test scripts.

Recommended Actions:
  1. Review the CVE details at NVD
  2. Check vendor security advisories for your specific version
  3. Test if the vulnerability is exploitable in your environment
  4. Consider updating to the latest version as a precaution

⚠️ Risk & Real-World Impact

🔴

Worst Case

Remote code execution leading to complete PLC compromise, manipulation of industrial processes, physical damage, or safety incidents

🟠

Likely Case

Denial of service causing PLC crashes and disruption of industrial operations

🟢

If Mitigated

Limited impact if PLCs are isolated from untrusted networks and have proper network segmentation

🌐 Internet-Facing: HIGH - If PLCs are directly exposed to the internet, they can be remotely exploited via Modbus/TCP
🏢 Internal Only: MEDIUM - Requires network access but Modbus is commonly used in industrial networks

🎯 Exploit Status

Public PoC: ⚠️ Yes
Weaponized: LIKELY
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Public GitHub repository contains vulnerability details. Modbus protocol is unauthenticated by design, making exploitation straightforward.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Unknown

Vendor Advisory: Not available

Restart Required: Yes

Instructions:

1. Contact Inovance for firmware updates. 2. Backup PLC configuration. 3. Apply firmware update via programming software. 4. Restart PLC. 5. Verify functionality.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate PLCs from untrusted networks using firewalls

Modbus Port Restriction

linux

Block external access to Modbus TCP port 502

iptables -A INPUT -p tcp --dport 502 -j DROP

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate PLCs from untrusted networks
  • Deploy industrial firewall with deep packet inspection for Modbus traffic

🔍 How to Verify

Check if Vulnerable:

Check PLC firmware version via programming software or web interface. If version matches affected list, system is vulnerable.

Check Version:

Use Inovance AutoShop programming software to read PLC version information

Verify Fix Applied:

Verify firmware version has been updated to a version not in the affected list

📡 Detection & Monitoring

Log Indicators:

  • PLC crash/restart events
  • Unusual Modbus traffic patterns
  • Buffer overflow errors in PLC logs

Network Indicators:

  • Malformed Modbus packets to port 502
  • Unusual source IPs accessing PLCs
  • Excessive connection attempts

SIEM Query:

source_port:502 AND (packet_size > normal_threshold OR malformed_protocol:true)

🔗 References