CVE-2024-30209

9.6 CRITICAL

📋 TL;DR

This vulnerability in Siemens SIMATIC RTLS Locating Manager allows attackers to eavesdrop on and modify client-server communications due to insufficient cryptographic protection of transmitted resources. An attacker positioned in the network path between server and client (Man-in-the-Middle) can intercept and manipulate data. All versions before V3.0.1.1 of multiple SIMATIC RTLS Locating Manager products are affected.

💻 Affected Systems

Products:
  • SIMATIC RTLS Locating Manager (6GT2780-0DA00)
  • SIMATIC RTLS Locating Manager (6GT2780-0DA10)
  • SIMATIC RTLS Locating Manager (6GT2780-0DA20)
  • SIMATIC RTLS Locating Manager (6GT2780-0DA30)
  • SIMATIC RTLS Locating Manager (6GT2780-1EA10)
  • SIMATIC RTLS Locating Manager (6GT2780-1EA20)
  • SIMATIC RTLS Locating Manager (6GT2780-1EA30)
Versions: All versions < V3.0.1.1
Operating Systems: Windows
Default Config Vulnerable: ⚠️ Yes
Notes: Requires attacker to be in network path between RTLS server and client (MitM position).

⚠️ Manual Verification Required

This CVE does not have specific version information in our database, so automatic vulnerability detection cannot determine if your system is affected.

Why? The CVE database entry doesn't specify which versions are vulnerable (no version ranges provided by the vendor/NVD).

🔒 Custom verification scripts are available for registered users. Sign up free to download automated test scripts.

Recommended Actions:
  1. Review the CVE details at NVD
  2. Check vendor security advisories for your specific version
  3. Test if the vulnerability is exploitable in your environment
  4. Consider updating to the latest version as a precaution

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete compromise of RTLS system integrity and confidentiality, allowing attackers to manipulate location data, inject malicious resources, or disrupt operations in critical industrial environments.

🟠

Likely Case

Data interception and modification of RTLS communications, potentially leading to inaccurate location tracking, operational disruption, or information disclosure.

🟢

If Mitigated

Limited impact with proper network segmentation and monitoring, though the fundamental vulnerability remains until patched.

🌐 Internet-Facing: MEDIUM
🏢 Internal Only: HIGH

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires network access and MitM position, but no authentication or special privileges needed once positioned.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: V3.0.1.1

Vendor Advisory: https://cert-portal.siemens.com/productcert/html/ssa-093430.html

Restart Required: Yes

Instructions:

1. Download V3.0.1.1 from Siemens support portal. 2. Backup current configuration. 3. Install update following Siemens documentation. 4. Restart system. 5. Verify version and functionality.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate RTLS systems from untrusted networks and implement strict network access controls.

VPN/Encrypted Tunnel

all

Use VPN or encrypted tunnels for all RTLS client-server communications.

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate RTLS systems from potential attackers.
  • Deploy network monitoring and intrusion detection for unusual traffic patterns between RTLS components.

🔍 How to Verify

Check if Vulnerable:

Check installed version in RTLS Locating Manager interface or Windows Programs and Features. If version is below V3.0.1.1, system is vulnerable.

Check Version:

Check via RTLS Locating Manager GUI or Windows Control Panel > Programs and Features

Verify Fix Applied:

Confirm version shows V3.0.1.1 or higher in system interface. Test client-server communications for proper encryption.

📡 Detection & Monitoring

Log Indicators:

  • Unusual network connection patterns between RTLS components
  • Failed or unusual authentication attempts to RTLS services

Network Indicators:

  • Unencrypted or suspicious traffic between RTLS server and clients
  • Unexpected network devices in RTLS communication path

SIEM Query:

source="rtls_server" AND (protocol="http" OR protocol="unencrypted") AND dest="rtls_client"

🔗 References

📤 Share & Export