CVE-2023-2262

9.8 CRITICAL

📋 TL;DR

A buffer overflow vulnerability in Rockwell Automation 1756-EN* communication devices allows remote code execution via malicious CIP requests. This affects industrial control systems using these specific communication modules. Successful exploitation could give attackers control over critical industrial equipment.

💻 Affected Systems

Products:
  • Rockwell Automation 1756-EN2T
  • 1756-EN2TR
  • 1756-EN2TP
  • 1756-EN2TRXT
  • 1756-EN2TPXT
  • 1756-EN2F
  • 1756-EN2TRF
  • 1756-EN2TPF
  • 1756-EN2TRXTK
  • 1756-EN2TPXTK
Versions: All versions prior to firmware version 6.011
Operating Systems: Embedded firmware on communication modules
Default Config Vulnerable: ⚠️ Yes
Notes: Affects specific 1756-EN* series communication modules used in ControlLogix systems

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete compromise of industrial control systems leading to physical damage, production shutdown, or safety incidents

🟠

Likely Case

Unauthorized access to industrial networks, data exfiltration, or disruption of manufacturing processes

🟢

If Mitigated

Limited impact if network segmentation and access controls prevent malicious traffic from reaching devices

🌐 Internet-Facing: HIGH - Devices exposed to internet are directly vulnerable to remote exploitation
🏢 Internal Only: HIGH - Internal attackers or compromised internal systems can exploit this vulnerability

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: MEDIUM

Exploitation requires sending specially crafted CIP requests to vulnerable devices

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Firmware version 6.011

Vendor Advisory: https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140786

Restart Required: Yes

Instructions:

1. Download firmware version 6.011 from Rockwell Automation website. 2. Use ControlFLASH or Studio 5000 Logix Designer to update firmware. 3. Restart affected devices after firmware update.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate affected devices in separate network segments with strict firewall rules

CIP Traffic Filtering

all

Implement firewall rules to block unnecessary CIP traffic to vulnerable devices

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate affected devices
  • Deploy intrusion detection systems to monitor for malicious CIP traffic

🔍 How to Verify

Check if Vulnerable:

Check firmware version on 1756-EN* devices using Studio 5000 Logix Designer or RSLinx Classic

Check Version:

Use Studio 5000 Logix Designer: Right-click module > Properties > Module Info

Verify Fix Applied:

Verify firmware version shows 6.011 or higher after update

📡 Detection & Monitoring

Log Indicators:

  • Unusual CIP protocol traffic patterns
  • Multiple failed CIP connection attempts
  • Unexpected firmware modification attempts

Network Indicators:

  • Malformed CIP packets to port 44818
  • Unusual CIP service requests
  • Traffic from unauthorized sources to industrial network segments

SIEM Query:

source_port:44818 AND (protocol:CIP OR service:cip) AND (malformed_packet:true OR buffer_overflow_attempt:true)

🔗 References

📤 Share & Export