CVE-2023-1834

9.4 CRITICAL

📋 TL;DR

Rockwell Automation Kinetix 5500 drives manufactured between May 2022 and January 2023 with firmware v7.13 have telnet and FTP ports open by default, allowing unauthorized network access. This affects industrial control systems using these specific drives, potentially exposing them to remote attackers.

💻 Affected Systems

Products:
  • Rockwell Automation Kinetix 5500 drives
Versions: Firmware version 7.13
Operating Systems: Embedded firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Only drives manufactured between May 2022 and January 2023 with v7.13 firmware are affected. Other versions or manufacturing dates are not vulnerable.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Attackers gain full control of industrial drives, potentially disrupting manufacturing processes, causing equipment damage, or manipulating production parameters.

🟠

Likely Case

Unauthorized access to drive configuration and operational data, potential firmware modification, or denial of service to connected machinery.

🟢

If Mitigated

Limited exposure if drives are isolated in protected networks with proper segmentation and access controls.

🌐 Internet-Facing: HIGH
🏢 Internal Only: MEDIUM

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires only network access to telnet/FTP ports - no authentication needed. Attackers can connect directly if ports are accessible.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Firmware version 7.14 or later

Vendor Advisory: https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1139441

Restart Required: Yes

Instructions:

1. Download firmware v7.14+ from Rockwell Automation website. 2. Backup current configuration. 3. Update firmware using Studio 5000 Logix Designer. 4. Verify ports are closed after update. 5. Restart drive.

🔧 Temporary Workarounds

Network Access Control

all

Block telnet (port 23) and FTP (port 21) traffic at network perimeter and internal segmentation points

Firewall Rules

all

Implement strict firewall rules to only allow necessary traffic to Kinetix drives from authorized sources

🧯 If You Can't Patch

  • Isolate affected drives in separate VLAN with strict access controls
  • Implement network monitoring for telnet/FTP traffic to these devices

🔍 How to Verify

Check if Vulnerable:

Check manufacturing date on drive label (May 2022-Jan 2023) and verify firmware version is 7.13 via Studio 5000 or drive display

Check Version:

Use Studio 5000 Logix Designer to read drive firmware version

Verify Fix Applied:

After updating to v7.14+, verify telnet and FTP ports are closed using port scanner or network monitoring

📡 Detection & Monitoring

Log Indicators:

  • Unexpected telnet/FTP connection attempts to drive IPs
  • Failed authentication attempts if credentials are set

Network Indicators:

  • Telnet (port 23) or FTP (port 21) traffic to Kinetix 5500 drives
  • Unusual traffic patterns to industrial network segments

SIEM Query:

source_ip IN (industrial_network_range) AND (destination_port:23 OR destination_port:21)

🔗 References

📤 Share & Export