CVE-2022-31206

9.8 CRITICAL

📋 TL;DR

CVE-2022-31206 allows attackers to upload and execute arbitrary machine code on Omron SYSMAC PLCs due to lack of cryptographic authentication for downloaded logic. This affects all Omron SYSMAC Nx product family PLCs (NJ, NY, NX, PMAC series) through 2022-05-18. Industrial control system operators using these PLCs are at risk of unauthorized code execution.

💻 Affected Systems

Products:
  • Omron SYSMAC NJ series
  • Omron SYSMAC NY series
  • Omron SYSMAC NX series
  • Omron SYSMAC PMAC series
Versions: All versions through 2022-05-18
Operating Systems: Real-time operating system (RTOS) specific to Omron PLCs
Default Config Vulnerable: ⚠️ Yes
Notes: Vulnerability exists in the programming/engineering workflow where logic is downloaded to PLCs without cryptographic verification.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete compromise of PLC allowing arbitrary code execution, potential physical process manipulation, safety system bypass, and lateral movement to other industrial systems.

🟠

Likely Case

Unauthorized logic modification leading to process disruption, data manipulation, or denial of service in industrial operations.

🟢

If Mitigated

Limited impact if network segmentation and access controls prevent unauthorized connections to PLC programming ports.

🌐 Internet-Facing: HIGH - Direct internet exposure allows remote attackers to upload malicious code without authentication.
🏢 Internal Only: HIGH - Internal attackers or compromised systems can exploit this vulnerability to manipulate industrial processes.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: LIKELY
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires network access to PLC programming ports but no authentication. Attack tools for industrial protocols are increasingly available.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Not available

Vendor Advisory: https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02

Restart Required: No

Instructions:

No official patch exists. Follow CISA ICS advisory recommendations for mitigation and workarounds.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate PLCs in dedicated industrial network segments with strict firewall rules

Access Control Lists

all

Implement strict IP-based access controls allowing only authorized engineering stations to connect to PLC programming ports

🧯 If You Can't Patch

  • Implement network monitoring for unauthorized connections to PLC programming ports (typically TCP 9600)
  • Use application allowlisting on engineering workstations to prevent unauthorized SYSMAC Studio usage

🔍 How to Verify

Check if Vulnerable:

Check if you have Omron SYSMAC NJ/NY/NX/PMAC series PLCs manufactured before May 2022

Check Version:

Check PLC firmware version via SYSMAC Studio software

Verify Fix Applied:

Verify network segmentation prevents unauthorized access to PLC programming interfaces

📡 Detection & Monitoring

Log Indicators:

  • Unauthorized connection attempts to TCP port 9600
  • Multiple failed programming sessions
  • Unexpected logic download events

Network Indicators:

  • Unusual traffic patterns to PLC programming ports
  • Connections from unauthorized IP addresses to industrial network segments

SIEM Query:

source_ip NOT IN (authorized_engineering_stations) AND dest_port=9600 AND protocol=TCP

🔗 References