CVE-2022-29884

7.5 HIGH

📋 TL;DR

This vulnerability affects Siemens CP-8000 and CP-8021/8022 master modules running firmware versions below CPC80 V16.30. An unauthenticated remote attacker can trigger a resource exhaustion condition in the HTTPS server, causing denial of service. This impacts industrial control systems using these specific automation devices.

💻 Affected Systems

Products:
  • CP-8000 MASTER MODULE WITH I/O -25/+70°C
  • CP-8000 MASTER MODULE WITH I/O -40/+70°C
  • CP-8021 MASTER MODULE
  • CP-8022 MASTER MODULE WITH GPRS
Versions: All versions < CPC80 V16.30
Operating Systems: Embedded firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Vulnerability requires HTTPS server to be enabled and accessible. Devices in default configurations with network exposure are vulnerable.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Critical industrial processes become unavailable due to device failure, potentially causing production shutdowns, safety system disruptions, or environmental impacts.

🟠

Likely Case

Targeted devices become unresponsive and require manual restart, disrupting automation processes until service is restored.

🟢

If Mitigated

With proper network segmentation and monitoring, impact is limited to isolated network segments with minimal operational disruption.

🌐 Internet-Facing: HIGH
🏢 Internal Only: MEDIUM

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires network access to the HTTPS service but no authentication. The specific conditions mentioned in the advisory suggest targeted traffic patterns are needed.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: CPC80 V16.30 or later

Vendor Advisory: https://cert-portal.siemens.com/productcert/pdf/ssa-491621.pdf

Restart Required: Yes

Instructions:

1. Download CPC80 V16.30 or later firmware from Siemens support portal. 2. Backup device configuration. 3. Apply firmware update following Siemens documentation. 4. Verify successful update and restore configuration. 5. Test device functionality.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate affected devices in dedicated network segments with strict firewall rules limiting HTTPS access.

Disable HTTPS Server

all

If HTTPS functionality is not required, disable the HTTPS server interface on affected devices.

🧯 If You Can't Patch

  • Implement strict network access controls allowing only trusted sources to connect to HTTPS service
  • Deploy network monitoring and intrusion detection systems to detect DoS attempts

🔍 How to Verify

Check if Vulnerable:

Check device firmware version via web interface or diagnostic tools. If version is below CPC80 V16.30 and HTTPS server is enabled, device is vulnerable.

Check Version:

Use Siemens TIA Portal or device web interface to check firmware version

Verify Fix Applied:

Verify firmware version shows CPC80 V16.30 or later in device management interface.

📡 Detection & Monitoring

Log Indicators:

  • Repeated HTTPS connection attempts
  • Device resource exhaustion warnings
  • Unexpected device restarts

Network Indicators:

  • Unusual HTTPS traffic patterns to industrial devices
  • Multiple connection attempts from single sources

SIEM Query:

source_ip:industrial_device AND protocol:HTTPS AND (event_type:connection_failure OR event_type:resource_warning)

🔗 References

📤 Share & Export