CVE-2022-29878

7.5 HIGH

📋 TL;DR

This vulnerability allows unauthenticated attackers to bypass authentication on SICAM T devices by capturing and replaying challenge-response pairs. Attackers can gain access to the management interface by waiting for a previously captured challenge to reappear. All SICAM T devices running versions before V3.0 are affected.

💻 Affected Systems

Products:
  • SICAM T
Versions: All versions < V3.0
Operating Systems: Embedded/Proprietary
Default Config Vulnerable: ⚠️ Yes
Notes: Affects the unencrypted challenge-response authentication mechanism used in the management interface.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete compromise of device management interface leading to unauthorized configuration changes, disruption of operations, or lateral movement within industrial control systems.

🟠

Likely Case

Unauthorized access to management interface allowing configuration changes, monitoring of sensitive data, or disruption of device functionality.

🟢

If Mitigated

Limited impact if devices are isolated from untrusted networks and have additional authentication layers.

🌐 Internet-Facing: HIGH - Directly exploitable over network without authentication.
🏢 Internal Only: HIGH - Exploitable from any network segment with access to the device.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: LIKELY
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Attack requires network access to capture challenge-response pairs and repeated connection attempts to wait for known challenge.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: V3.0 or later

Vendor Advisory: https://cert-portal.siemens.com/productcert/html/ssa-165073.html

Restart Required: Yes

Instructions:

1. Download SICAM T V3.0 or later from Siemens support portal. 2. Backup current configuration. 3. Apply firmware update following Siemens documentation. 4. Verify successful update and restore configuration if needed.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate SICAM T devices from untrusted networks and restrict access to management interfaces.

Access Control Lists

all

Implement strict firewall rules to limit which IP addresses can access the management interface.

🧯 If You Can't Patch

  • Implement network segmentation to isolate vulnerable devices from untrusted networks
  • Deploy intrusion detection systems to monitor for authentication bypass attempts

🔍 How to Verify

Check if Vulnerable:

Check device firmware version via web interface or CLI. If version is below V3.0, device is vulnerable.

Check Version:

Check via web interface at http(s)://device-ip/ or consult Siemens documentation for CLI commands.

Verify Fix Applied:

Verify firmware version is V3.0 or higher via device interface or management software.

📡 Detection & Monitoring

Log Indicators:

  • Multiple failed authentication attempts followed by successful login from same IP
  • Authentication requests with unusual timing patterns

Network Indicators:

  • Repeated HTTP/HTTPS requests to management interface from external IPs
  • Unusual traffic patterns to challenge-response endpoints

SIEM Query:

source_ip=external AND dest_port=80,443 AND url_path CONTAINS 'login' OR 'challenge' AND count > threshold

🔗 References