CVE-2022-24310

9.8 CRITICAL

📋 TL;DR

This vulnerability allows attackers to trigger an integer overflow leading to heap-based buffer overflow in Schneider Electric's Interactive Graphical SCADA System Data Server. Successful exploitation could cause denial of service or potentially remote code execution. Organizations using affected versions of this SCADA system are at risk.

💻 Affected Systems

Products:
  • Interactive Graphical SCADA System Data Server
Versions: V15.0.0.22020 and prior versions
Operating Systems: Windows (typically used for SCADA systems)
Default Config Vulnerable: ⚠️ Yes
Notes: This affects the core data server component of the SCADA system. Industrial control systems using this software in critical infrastructure are particularly vulnerable.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Remote code execution with SYSTEM/root privileges, allowing complete compromise of the SCADA system and potential lateral movement to other industrial control systems.

🟠

Likely Case

Denial of service causing SCADA system crashes and disruption of industrial operations, with potential for limited remote code execution in sophisticated attacks.

🟢

If Mitigated

Limited impact with proper network segmentation and access controls, potentially only causing service disruption without system compromise.

🌐 Internet-Facing: HIGH - SCADA systems exposed to internet are extremely vulnerable to remote exploitation via crafted messages.
🏢 Internal Only: HIGH - Even internally, attackers with network access can exploit this vulnerability to compromise critical infrastructure systems.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: LIKELY
Unauthenticated Exploit: ⚠️ Yes
Complexity: MEDIUM

The vulnerability requires sending specially crafted messages but does not require authentication. Given the critical nature of SCADA systems, exploitation tools are likely developed by advanced threat actors.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Versions after V15.0.0.22020

Vendor Advisory: https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-039-01

Restart Required: Yes

Instructions:

1. Download the updated version from Schneider Electric's security advisory. 2. Backup current configuration and data. 3. Install the updated version following vendor instructions. 4. Restart the SCADA Data Server service. 5. Verify proper functionality.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate SCADA systems from untrusted networks using firewalls and network segmentation

Access Control Restrictions

all

Implement strict network access controls to limit who can communicate with the SCADA Data Server

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate SCADA systems from all untrusted networks
  • Deploy intrusion detection/prevention systems to monitor for anomalous traffic patterns and block suspicious messages

🔍 How to Verify

Check if Vulnerable:

Check the software version in the SCADA system administration interface or via Windows Programs and Features. If version is V15.0.0.22020 or earlier, the system is vulnerable.

Check Version:

Check via SCADA administration console or Windows Control Panel > Programs and Features

Verify Fix Applied:

Verify the installed version is newer than V15.0.0.22020 and check system logs for any abnormal activity or crashes after patch installation.

📡 Detection & Monitoring

Log Indicators:

  • Multiple connection attempts with malformed messages
  • SCADA Data Server service crashes or restarts
  • Memory allocation errors in application logs

Network Indicators:

  • Unusual volume of messages to SCADA Data Server port
  • Messages with abnormal size or structure patterns

SIEM Query:

source="scada_server" AND (event_type="crash" OR event_type="memory_error" OR message_count > threshold)

🔗 References

📤 Share & Export