CVE-2021-31892

7.4 HIGH

📋 TL;DR

This vulnerability in multiple Siemens SINUMERIK industrial software products allows man-in-the-middle attacks due to improper SSL/TLS certificate validation. Attackers could intercept and manipulate encrypted communications between affected software and servers. All listed SINUMERIK products with specified versions are affected.

💻 Affected Systems

Products:
  • SINUMERIK Analyse MyCondition
  • SINUMERIK Analyze MyPerformance
  • SINUMERIK Analyze MyPerformance /OEE-Monitor
  • SINUMERIK Analyze MyPerformance /OEE-Tuning
  • SINUMERIK Integrate Client 02
  • SINUMERIK Integrate Client 03
  • SINUMERIK Integrate Client 04
  • SINUMERIK Integrate for Production 4.1
  • SINUMERIK Integrate for Production 5.1
  • SINUMERIK Manage MyMachines
  • SINUMERIK Manage MyMachines /Remote
  • SINUMERIK Manage MyMachines /Spindel Monitor
  • SINUMERIK Manage MyPrograms
  • SINUMERIK Manage MyResources /Programs
  • SINUMERIK Manage MyResources /Tools
  • SINUMERIK Manage MyTools
  • SINUMERIK Operate V4.8
  • SINUMERIK Operate V4.93
  • SINUMERIK Operate V4.94
  • SINUMERIK Optimize MyProgramming /NX-Cam Editor
Versions: All versions for most products, specific version ranges for Integrate Client (02: >=V02.00.12<02.00.18, 03: >=V03.00.12<03.00.18, 04: V04.00.02 and >=V04.00.15<04.00.18), Integrate for Production 4.1 (<V4.1 SP10 HF3), Operate V4.8 (<V4.8 SP8), Operate V4.93 (<V4.93 HF7), Operate V4.94 (<V4.94 HF5)
Operating Systems: Windows-based industrial control systems
Default Config Vulnerable: ⚠️ Yes
Notes: Vulnerability exists in third-party dependency affecting TLS/SSL certificate validation across multiple SINUMERIK products.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Attackers could intercept sensitive industrial control data, manipulate machine commands, steal credentials, or inject malicious code into manufacturing systems.

🟠

Likely Case

Data interception leading to intellectual property theft, operational data exposure, or credential harvesting for further attacks.

🟢

If Mitigated

Limited to internal network attacks only, with proper network segmentation preventing external exploitation.

🌐 Internet-Facing: MEDIUM - While these are industrial systems, some may have internet connectivity for remote monitoring/maintenance.
🏢 Internal Only: HIGH - Attackers on the same network could easily exploit this to intercept sensitive industrial communications.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires network access to intercept TLS traffic. No authentication needed as this is a protocol-level vulnerability.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Various - see Siemens advisory for specific product updates

Vendor Advisory: https://cert-portal.siemens.com/productcert/pdf/ssa-729965.pdf

Restart Required: Yes

Instructions:

1. Review Siemens advisory SSA-729965. 2. Identify affected products in your environment. 3. Apply vendor-provided updates for each affected product. 4. Restart systems as required. 5. Verify TLS certificate validation is functioning correctly.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate affected systems from untrusted networks to prevent MITM attacks

VPN/Encrypted Tunnel

all

Use VPN or encrypted tunnels for all communications between affected systems and servers

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate affected systems
  • Monitor network traffic for unusual TLS handshake patterns or certificate validation failures

🔍 How to Verify

Check if Vulnerable:

Check installed SINUMERIK product versions against affected versions list in Siemens advisory

Check Version:

Check version through SINUMERIK software interface or Windows installed programs list

Verify Fix Applied:

Test TLS connections to verify server certificates are properly validated after patching

📡 Detection & Monitoring

Log Indicators:

  • TLS handshake failures
  • Certificate validation errors
  • Unexpected certificate authorities

Network Indicators:

  • Unencrypted fallback attempts
  • TLS version downgrades
  • Suspicious MITM patterns in network traffic

SIEM Query:

tls.handshake.type:1 AND (NOT tls.handshake.extensions_server_name OR tls.handshake.certificate_verify:0)