CVE-2021-27391
📋 TL;DR
This CVE describes a critical buffer overflow vulnerability in Siemens APOGEE and TALON building automation controllers. Unauthenticated remote attackers can exploit improper bounds checking in the HTTP Host parameter parsing to execute arbitrary code with root privileges. Affected devices include various APOGEE MBC, MEC, PXC Compact/Modular and TALON TC Compact/Modular controllers with specific firmware versions.
💻 Affected Systems
- APOGEE MBC (PPC) (P2 Ethernet)
- APOGEE MEC (PPC) (P2 Ethernet)
- APOGEE PXC Compact (BACnet)
- APOGEE PXC Compact (P2 Ethernet)
- APOGEE PXC Modular (BACnet)
- APOGEE PXC Modular (P2 Ethernet)
- TALON TC Compact (BACnet)
- TALON TC Modular (BACnet)
📦 What is this software?
Apogee Mbc \(ppc\) \(p2 Ethernet\) Firmware by Siemens
View all CVEs affecting Apogee Mbc \(ppc\) \(p2 Ethernet\) Firmware →
Apogee Mec \(ppc\) \(p2 Ethernet\) Firmware by Siemens
View all CVEs affecting Apogee Mec \(ppc\) \(p2 Ethernet\) Firmware →
Apogee Pxc Bacnet Automation Controller Firmware by Siemens
View all CVEs affecting Apogee Pxc Bacnet Automation Controller Firmware →
Apogee Pxc Compact \(p2 Ethernet\) Firmware by Siemens
View all CVEs affecting Apogee Pxc Compact \(p2 Ethernet\) Firmware →
Apogee Pxc Modular \(bacnet\) Firmware by Siemens
View all CVEs affecting Apogee Pxc Modular \(bacnet\) Firmware →
Apogee Pxc Modular \(p2 Ethernet\) Firmware by Siemens
View all CVEs affecting Apogee Pxc Modular \(p2 Ethernet\) Firmware →
⚠️ Risk & Real-World Impact
Worst Case
Complete system compromise with root-level code execution, allowing attackers to take full control of building automation systems, manipulate HVAC controls, disable safety systems, or pivot to other network segments.
Likely Case
Remote code execution leading to disruption of building operations, data exfiltration, or ransomware deployment on critical infrastructure systems.
If Mitigated
Limited impact if devices are behind firewalls with strict network segmentation and proper access controls, though the vulnerability remains exploitable by authorized internal users.
🎯 Exploit Status
The vulnerability is unauthenticated and requires only HTTP access, making exploitation straightforward for attackers with network access to vulnerable devices.
🛠️ Fix & Mitigation
✅ Official Fix
Patch Version: APOGEE PXC Compact/Modular (BACnet): V3.5.3 or later; TALON TC Compact/Modular (BACnet): V3.5.3 or later; APOGEE MBC/MEC (P2 Ethernet): Update to latest available version; APOGEE PXC Compact/Modular (P2 Ethernet): Update to latest available version
Vendor Advisory: https://cert-portal.siemens.com/productcert/pdf/ssa-944498.pdf
Restart Required: Yes
Instructions:
1. Download firmware updates from Siemens Industry Online Support; 2. Backup device configuration; 3. Apply firmware update following Siemens documentation; 4. Restart device; 5. Verify firmware version and functionality.
🔧 Temporary Workarounds
Network Segmentation and Access Control
allRestrict network access to affected devices using firewalls and VLAN segmentation
Disable Web Interface
allDisable HTTP/HTTPS web server if not required for operations
🧯 If You Can't Patch
- Implement strict network segmentation to isolate affected devices from untrusted networks
- Deploy intrusion detection systems to monitor for exploitation attempts and anomalous HTTP traffic
🔍 How to Verify
Check if Vulnerable:
Check device firmware version via web interface or management console and compare against affected versions listed in vendor advisory
Check Version:
Check via device web interface or Siemens management tools (specific commands vary by device model)
Verify Fix Applied:
Verify firmware version is updated to patched versions: APOGEE PXC/TALON TC (BACnet) >= V3.5.3; APOGEE MBC/MEC/PXC (P2 Ethernet) latest available version
📡 Detection & Monitoring
Log Indicators:
- Unusual HTTP requests with malformed Host headers
- Multiple failed buffer overflow attempts in web server logs
- Unexpected process creation or system reboots
Network Indicators:
- HTTP requests with unusually long Host headers to building automation controllers
- Traffic to/from building automation systems from unauthorized IP addresses
SIEM Query:
source="web_server_logs" AND (Host:*[>1024] OR "buffer overflow" OR "segmentation fault")