CVE-2021-22778

7.1 HIGH

📋 TL;DR

This vulnerability allows unauthorized users to read or modify protected function blocks in Schneider Electric industrial control software when accessing project files. It affects EcoStruxure Control Expert, EcoStruxure Process Expert, and SCADAPack RemoteConnect systems. Attackers could potentially alter industrial control logic or steal sensitive configuration data.

💻 Affected Systems

Products:
  • EcoStruxure Control Expert
  • EcoStruxure Process Expert
  • SCADAPack RemoteConnect for x70
Versions: All versions prior to V15.0 SP1 for Control Expert; all versions for Process Expert and SCADAPack RemoteConnect
Operating Systems: Windows
Default Config Vulnerable: ⚠️ Yes
Notes: Unity Pro versions are also affected as they are part of the Control Expert product line.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Attackers could modify control logic in critical infrastructure systems, potentially causing physical damage, production shutdowns, or safety incidents by altering protected function blocks.

🟠

Likely Case

Unauthorized access to sensitive project files leading to intellectual property theft, configuration tampering, or reconnaissance for further attacks on industrial control systems.

🟢

If Mitigated

Limited impact with proper access controls, network segmentation, and project file encryption preventing unauthorized access to vulnerable files.

🌐 Internet-Facing: MEDIUM - While the vulnerability requires project file access, internet-exposed systems with file sharing capabilities could be targeted.
🏢 Internal Only: HIGH - Internal attackers or compromised accounts with access to project files could exploit this vulnerability to modify industrial control logic.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ✅ No
Complexity: MEDIUM

Exploitation requires access to project files, which typically requires some level of system access or file sharing permissions.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: V15.0 SP1 for EcoStruxure Control Expert; check vendor advisory for other products

Vendor Advisory: http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-194-01

Restart Required: Yes

Instructions:

1. Download the appropriate patch from Schneider Electric's security advisory. 2. Backup all project files. 3. Install the patch following vendor instructions. 4. Restart affected systems. 5. Verify patch installation and test functionality.

🔧 Temporary Workarounds

Restrict Project File Access

windows

Implement strict access controls on project files and directories to prevent unauthorized access.

Set appropriate file permissions using Windows ACLs or equivalent

Network Segmentation

all

Isolate industrial control systems from business networks and implement strict firewall rules.

🧯 If You Can't Patch

  • Implement strict access controls on all project files and directories
  • Use encryption for project file storage and transmission
  • Monitor for unauthorized access attempts to project files
  • Implement application whitelisting to prevent unauthorized software execution

🔍 How to Verify

Check if Vulnerable:

Check software version against affected versions list. For Control Expert: versions prior to V15.0 SP1 are vulnerable.

Check Version:

Check version in software 'About' dialog or installation directory properties

Verify Fix Applied:

Verify installed version is V15.0 SP1 or later for Control Expert. Check vendor advisory for other product updates.

📡 Detection & Monitoring

Log Indicators:

  • Unauthorized access attempts to project files
  • Unexpected modifications to .pro or project files
  • Failed authentication attempts to engineering workstations

Network Indicators:

  • Unexpected file transfers of project files
  • Unauthorized access to engineering network segments

SIEM Query:

EventID:4625 OR (FileAccess AND Extension:'.pro') OR (ProcessCreation AND ParentImage:'*ControlExpert*')

🔗 References