CVE-2021-22699

7.5 HIGH

📋 TL;DR

An improper input validation vulnerability in Schneider Electric Modicon M241/M251 logic controllers allows attackers to cause denial of service via specially crafted HTTP requests. This affects organizations using these industrial controllers with firmware versions before V5.1.9.1 in their operational technology environments.

💻 Affected Systems

Products:
  • Schneider Electric Modicon M241 logic controller
  • Schneider Electric Modicon M251 logic controller
Versions: All firmware versions prior to V5.1.9.1
Operating Systems: Embedded controller firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Affects controllers with HTTP interface enabled (default configuration). Industrial control systems using these controllers in manufacturing, energy, or critical infrastructure are particularly vulnerable.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete controller unavailability leading to production stoppage, safety system disruption, or process control failure in industrial environments.

🟠

Likely Case

Temporary controller unavailability requiring manual reboot, causing production delays and potential equipment damage.

🟢

If Mitigated

Minimal impact with proper network segmentation and monitoring detecting attack attempts before successful exploitation.

🌐 Internet-Facing: HIGH - HTTP interface is typically exposed and vulnerable to remote exploitation without authentication.
🏢 Internal Only: HIGH - Even internally, the vulnerability can be exploited by compromised devices or malicious insiders.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

Exploitation requires sending crafted HTTP requests to the controller's web interface. No authentication is required, making exploitation straightforward for attackers with network access.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: V5.1.9.1 or later

Vendor Advisory: https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-130-05

Restart Required: Yes

Instructions:

1. Download firmware V5.1.9.1 or later from Schneider Electric website. 2. Backup current controller configuration. 3. Upload new firmware using EcoStruxure Machine Expert software. 4. Restart controller. 5. Verify firmware version and restore configuration if needed.

🔧 Temporary Workarounds

Disable HTTP Interface

all

Disable the HTTP web server interface if not required for operations

Configure via EcoStruxure Machine Expert: Disable HTTP server in controller settings

Network Segmentation

all

Isolate controllers in separate VLAN with strict firewall rules

Add firewall rule: deny all HTTP traffic to controller IP except from authorized engineering stations

🧯 If You Can't Patch

  • Implement strict network access controls allowing only authorized engineering stations to communicate with controllers
  • Deploy network intrusion detection systems monitoring for anomalous HTTP traffic patterns to controller IPs

🔍 How to Verify

Check if Vulnerable:

Check firmware version via EcoStruxure Machine Expert or web interface. If version is below V5.1.9.1, system is vulnerable.

Check Version:

Using EcoStruxure Machine Expert: Connect to controller → Controller → Properties → Firmware version

Verify Fix Applied:

Confirm firmware version shows V5.1.9.1 or higher in controller properties. Test HTTP interface functionality remains operational.

📡 Detection & Monitoring

Log Indicators:

  • Multiple HTTP 400/500 errors from controller
  • Controller reboot events without scheduled maintenance
  • Unusual HTTP request patterns to controller IP

Network Indicators:

  • HTTP requests with malformed headers or unusual payloads to controller port 80/8080
  • Sudden increase in HTTP traffic to industrial controllers

SIEM Query:

source="controller_logs" AND (http_status>=400 OR event_type="reboot") | stats count by src_ip, dest_ip

🔗 References