CVE-2021-22681

9.8 CRITICAL

📋 TL;DR

This vulnerability allows unauthenticated attackers to bypass authentication mechanisms in Rockwell Automation industrial control systems. It affects multiple Logix controller families when used with vulnerable versions of Studio 5000 Logix Designer and RSLogix 5000 software. Attackers could gain unauthorized access to critical industrial control systems.

💻 Affected Systems

Products:
  • Rockwell Automation Studio 5000 Logix Designer
  • RSLogix 5000
  • CompactLogix 1768
  • CompactLogix 1769
  • CompactLogix 5370
  • CompactLogix 5380
  • CompactLogix 5480
  • ControlLogix 5550
  • ControlLogix 5560
  • ControlLogix 5570
  • ControlLogix 5580
  • DriveLogix 5560
  • DriveLogix 5730
  • 1794-L34
  • Compact GuardLogix 5370
  • Compact GuardLogix 5380
  • GuardLogix 5570
  • GuardLogix 5580
  • SoftLogix 5800
Versions: Studio 5000 Logix Designer: Versions 21+, RSLogix 5000: Versions 16-20
Operating Systems: Windows
Default Config Vulnerable: ⚠️ Yes
Notes: Affects communication between the software and controllers. All default configurations are vulnerable.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete compromise of industrial control systems leading to physical damage, production shutdown, safety system manipulation, or environmental harm.

🟠

Likely Case

Unauthorized access to industrial controllers allowing configuration changes, logic manipulation, data exfiltration, or denial of service.

🟢

If Mitigated

Limited impact if systems are properly segmented, monitored, and have additional authentication layers.

🌐 Internet-Facing: HIGH - If controllers are directly exposed to the internet, attackers can exploit this without authentication.
🏢 Internal Only: HIGH - Even internally, unauthenticated attackers on the network can exploit this vulnerability.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: LIKELY
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

CVSS 9.8 indicates critical severity with low attack complexity. No public exploit code is known, but the vulnerability is straightforward to exploit.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Studio 5000 Logix Designer v32.011+, RSLogix 5000 requires upgrade to Studio 5000

Vendor Advisory: https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1129798

Restart Required: Yes

Instructions:

1. Download and install Studio 5000 Logix Designer v32.011 or later from Rockwell Automation. 2. Update all affected controllers with new firmware. 3. Restart systems after patching. 4. Verify communication is restored.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate affected controllers and engineering workstations in separate network segments with strict firewall rules.

Access Control Lists

all

Implement ACLs to restrict communication to only authorized engineering workstations and controllers.

🧯 If You Can't Patch

  • Implement strict network segmentation and zero-trust architecture
  • Deploy intrusion detection systems and monitor for unauthorized access attempts

🔍 How to Verify

Check if Vulnerable:

Check software version in Studio 5000 Logix Designer or RSLogix 5000. Versions in affected ranges are vulnerable.

Check Version:

In Studio 5000: Help → About. In RSLogix 5000: Help → About RSLogix 5000.

Verify Fix Applied:

Verify Studio 5000 Logix Designer is v32.011 or later. Test authentication with controllers to ensure proper verification.

📡 Detection & Monitoring

Log Indicators:

  • Failed authentication attempts followed by successful access
  • Unauthorized IP addresses accessing controllers
  • Unexpected configuration changes

Network Indicators:

  • Unusual traffic patterns to controller ports
  • Communication from unauthorized sources to controllers

SIEM Query:

source_ip NOT IN (authorized_ips) AND dest_port IN (controller_ports) AND protocol=tcp

🔗 References

📤 Share & Export