CVE-2020-7566

7.3 HIGH

📋 TL;DR

This vulnerability allows attackers to break encryption keys used between EcoStruxure Machine - Basic software and Modicon M221 controllers by capturing network traffic. The weak random value generation makes cryptographic keys predictable. All Modicon M221 PLC users with these communication channels are affected.

💻 Affected Systems

Products:
  • Modicon M221 Programmable Logic Controller
Versions: All versions
Operating Systems: Not applicable - embedded industrial controller
Default Config Vulnerable: ⚠️ Yes
Notes: Affects all Modicon M221 references (product variants). Vulnerability exists in the communication protocol between EcoStruxure Machine - Basic software and the controller.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete compromise of industrial control system communications, allowing attackers to intercept, modify, or inject commands to PLCs, potentially causing physical damage or production disruption.

🟠

Likely Case

Unauthorized access to industrial control communications, enabling monitoring of sensitive industrial processes and potential manipulation of PLC operations.

🟢

If Mitigated

Limited impact with proper network segmentation and monitoring, though encryption remains vulnerable if traffic is captured.

🌐 Internet-Facing: MEDIUM - While industrial control systems shouldn't be internet-facing, misconfigurations could expose them. Exploitation requires traffic capture capability.
🏢 Internal Only: HIGH - Attackers with internal network access can capture traffic between engineering workstations and PLCs to break encryption and compromise control systems.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ✅ No
Complexity: MEDIUM

Exploitation requires network traffic capture capability and cryptographic analysis skills. No public exploit code has been released.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Firmware version 1.10.3.0 or later

Vendor Advisory: https://www.se.com/ww/en/download/document/SEVD-2020-315-05/

Restart Required: Yes

Instructions:

1. Download firmware update from Schneider Electric website. 2. Connect to M221 controller via EcoStruxure Machine - Basic software. 3. Upload new firmware to controller. 4. Restart controller to apply update.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate Modicon M221 controllers and engineering workstations on separate VLANs with strict access controls

Encrypted Tunnel

all

Use VPN or other encrypted tunnel for communication between engineering software and PLCs

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate PLC traffic from general network
  • Deploy network monitoring to detect unusual traffic patterns between engineering stations and PLCs

🔍 How to Verify

Check if Vulnerable:

Check firmware version on Modicon M221 controller via EcoStruxure Machine - Basic software. Versions below 1.10.3.0 are vulnerable.

Check Version:

Not applicable - version check performed through EcoStruxure Machine - Basic software interface

Verify Fix Applied:

Confirm firmware version is 1.10.3.0 or later in controller properties via EcoStruxure Machine - Basic software.

📡 Detection & Monitoring

Log Indicators:

  • Unusual connection attempts to Modicon M221 controllers
  • Multiple failed authentication attempts to engineering software

Network Indicators:

  • Unusual traffic patterns between engineering workstations and PLCs
  • Network sniffing tools detected on control network

SIEM Query:

source_ip="engineering_workstation" AND dest_ip="plc_network" AND protocol="modbus_tcp" AND bytes_transferred>threshold