CVE-2020-7502

7.5 HIGH

📋 TL;DR

This vulnerability allows remote attackers to cause a Denial of Service (DoS) on Schneider Electric Modicon M218 Logic Controllers by sending specially crafted TCP/IP packets. The out-of-bounds write vulnerability affects firmware versions 4.3 and earlier. Industrial control systems using these PLCs in manufacturing, infrastructure, or building automation are at risk.

💻 Affected Systems

Products:
  • Schneider Electric Modicon M218 Logic Controller
Versions: Firmware version 4.3 and prior
Operating Systems: Embedded controller firmware
Default Config Vulnerable: ⚠️ Yes
Notes: All M218 controllers running affected firmware versions are vulnerable when network-connected. Physical-only installations without network connectivity are not affected.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete controller crash requiring physical reset, disrupting industrial processes and potentially causing production downtime or safety issues in critical infrastructure.

🟠

Likely Case

Controller becomes unresponsive, requiring manual reboot and causing temporary disruption to automated processes.

🟢

If Mitigated

If network segmentation and firewall rules are properly configured, the attack surface is reduced, though internal threats remain possible.

🌐 Internet-Facing: HIGH - Direct internet exposure allows remote attackers to easily send crafted packets to trigger the vulnerability.
🏢 Internal Only: MEDIUM - Attackers with internal network access or compromised internal systems can exploit this vulnerability.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: UNKNOWN
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

The vulnerability requires sending crafted TCP/IP packets to the controller's network interface. No authentication is required, making exploitation straightforward for attackers with network access.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Firmware version 4.4 or later

Vendor Advisory: https://www.se.com/ww/en/download/document/SEVD-2020-161-01

Restart Required: Yes

Instructions:

1. Download firmware version 4.4 or later from Schneider Electric's website. 2. Connect to the M218 controller via programming software. 3. Backup current program and configuration. 4. Upload and install the new firmware. 5. Restore program and configuration. 6. Verify firmware version and functionality.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate M218 controllers in separate network segments with strict firewall rules

Access Control Lists

all

Implement ACLs to restrict TCP/IP traffic to only authorized sources

🧯 If You Can't Patch

  • Implement strict network segmentation to isolate controllers from untrusted networks
  • Deploy intrusion detection systems to monitor for anomalous TCP/IP traffic patterns

🔍 How to Verify

Check if Vulnerable:

Check firmware version via Schneider Electric programming software. If version is 4.3 or earlier, the system is vulnerable.

Check Version:

Use Schneider Electric SoMachine or EcoStruxure Machine Expert software to read controller firmware version

Verify Fix Applied:

After patching, verify firmware version shows 4.4 or later in the programming software and confirm normal controller operation.

📡 Detection & Monitoring

Log Indicators:

  • Controller restart logs
  • Network communication errors
  • Unexpected TCP/IP connection attempts

Network Indicators:

  • Unusual TCP packet patterns to controller IP
  • Multiple connection attempts from single source
  • Malformed TCP/IP packets

SIEM Query:

source_ip="controller_ip" AND (tcp_flags="malformed" OR packet_size>normal_range)

🔗 References

📤 Share & Export