CVE-2020-25195

7.5 HIGH

📋 TL;DR

This vulnerability allows attackers to bypass client-side input validation on Host Engineering ECOM100 modules, potentially causing device crashes through specially crafted web requests. It affects industrial control systems using H0-ECOM100, H2-ECOM100, and H4-ECOM100 communication modules. The lack of server-side validation makes exploitation straightforward.

💻 Affected Systems

Products:
  • Host Engineering H0-ECOM100
  • Host Engineering H2-ECOM100
  • Host Engineering H4-ECOM100
Versions: All versions prior to firmware update
Operating Systems: Embedded firmware
Default Config Vulnerable: ⚠️ Yes
Notes: Affects the web configuration interface of these industrial communication modules. The vulnerability exists in the web server component that handles configuration input.

📦 What is this software?

⚠️ Risk & Real-World Impact

🔴

Worst Case

Complete denial of service causing industrial process disruption, potentially leading to safety incidents or production downtime in critical infrastructure environments.

🟠

Likely Case

Device crash requiring manual reboot, causing temporary communication loss between PLCs and control systems.

🟢

If Mitigated

Minimal impact if devices are behind firewalls with restricted web access and proper network segmentation.

🌐 Internet-Facing: HIGH - Directly accessible web interfaces with no server-side validation make these devices easy targets for remote attacks.
🏢 Internal Only: MEDIUM - Internal attackers or malware could still exploit this, but requires network access to the vulnerable modules.

🎯 Exploit Status

Public PoC: ✅ No
Weaponized: LIKELY
Unauthenticated Exploit: ⚠️ Yes
Complexity: LOW

The advisory suggests exploitation is straightforward due to lack of server-side validation. No public exploit code was found in the references, but the simple nature makes weaponization likely.

🛠️ Fix & Mitigation

✅ Official Fix

Patch Version: Firmware update as specified in ICSA-20-345-02

Vendor Advisory: https://us-cert.cisa.gov/ics/advisories/icsa-20-345-02

Restart Required: Yes

Instructions:

1. Download firmware update from Host Engineering website. 2. Access device web interface. 3. Navigate to firmware update section. 4. Upload new firmware file. 5. Wait for update to complete. 6. Reboot device as prompted.

🔧 Temporary Workarounds

Network Segmentation

all

Isolate ECOM100 modules in separate VLANs with restricted access to configuration web interface

Access Control Lists

all

Implement firewall rules to restrict web interface access to authorized management stations only

🧯 If You Can't Patch

  • Disable web interface if not required for operations
  • Implement network monitoring for abnormal HTTP requests to device web ports

🔍 How to Verify

Check if Vulnerable:

Check firmware version via web interface and compare against patched versions in ICSA-20-345-02

Check Version:

Access device web interface at http://[device-ip] and navigate to system information page

Verify Fix Applied:

Verify firmware version shows updated version after patch installation

📡 Detection & Monitoring

Log Indicators:

  • Multiple connection attempts to web interface
  • Device reboot logs without scheduled maintenance

Network Indicators:

  • Unusual HTTP POST requests to device web ports (typically 80/443)
  • Traffic patterns suggesting buffer overflow attempts

SIEM Query:

source_ip="*" AND dest_port=80 AND http_method=POST AND uri_contains="config" AND bytes_sent>1000

🔗 References